Actual signals and parameters 235
3703 USER LOAD C
TIME
Defines the time limit for generating a fault. Half of this time
is used as the limit for generating an alarm.
20 s
10…400s Time 1=1s
3704 LOAD FREQ 1 Defines the frequency value of the first load curve definition
point. Must be smaller than 3707 LOAD FREQ 2.
5Hz
0…500 Hz Frequency 1 = 1 Hz
3705 LOAD TORQ
LOW 1
Defines the torque value of the first underload curve
definition point. Must be smaller than 3706 LOAD TORQ
HIGH 1.
10%
0…600% Torque 1 = 1%
3706 LOAD TORQ
HIGH 1
Defines the torque value of the first overload curve definition
point
300%
0…600% Torque 1 = 1%
3707 LOAD FREQ 2 Defines the frequency value of the second load curve
definition point. Must be smaller than 3710 LOAD FREQ 3.
25 Hz
0…500 Hz Frequency 1 = 1 Hz
3708 LOAD TORQ
LOW 2
Defines the torque value of the second underload curve
definition point. Must be smaller than 3709 LOAD TORQ
HIGH 2.
15%
0…600% Torque 1 = 1%
3709 LOAD TORQ
HIGH 2
Defines the torque value of the second overload curve
definition point
300%
0…600% Torque 1 = 1%
3710 LOAD FREQ 3 Defines the frequency value of the third load curve definition
point. Must be smaller than 3713 LOAD FREQ 4.
43 Hz
0…500 Hz Frequency 1 = 1 Hz
3711 LOAD TORQ
LOW 3
Defines the torque value of the third underload curve
definition point. Must be smaller than 3712 LOAD TORQ
HIGH 3.
25%
0…600% Torque 1 = 1%
3712 LOAD TORQ
HIGH 3
Defines the torque value of the third overload curve
definition point
300%
0…600% Torque 1 = 1%
3713 LOAD FREQ 4 Defines the frequency value of the fourth load curve
definition point. Must be smaller than 3716 LOAD FREQ 5.
50 Hz
0…500 Hz Frequency 1 = 1 Hz
3714 LOAD TORQ
LOW 4
Defines the torque value of the fourth underload curve
definition point. Must be smaller than 3715 LOAD TORQ
HIGH 4.
30%
0…600% Torque 1 = 1%
3715 LOAD TORQ
HIGH 4
Defi
nes the torque value of the fourth overload curve
definition point
300%
0…600% Torque 1 = 1%
3716 LOAD FREQ 5 Defines the frequency value of the fifth load curve definition
point
500 Hz
0…500 Hz Frequency 1 = 1 Hz
All parameters
No. Name/Value Description Def/FbEq
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for ABB ACS310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS310 and is the answer not in the manual?

ABB ACS310 Specifications

General IconGeneral
Frequency50/60 Hz
IP RatingIP20
Control MethodScalar control
EMC FilterBuilt-in
Supply Voltage200 to 240 V, 380 to 480 V

Related product manuals