60 Start-up and control with I/O
1. To go to the Main menu, press if the bottom
line shows OUTPUT; otherwise press
repeatedly until you see MENU at the bottom.
2. Press keys / until you see “PAr”, and
press .
3. Find the appropriate parameter group with keys
/ and press .
4. Find the appropriate parameter in the group with
keys / .
5. Press and hold for about two seconds until the
parameter value is shown with under the value.
6. Change the value with keys / . The value
changes faster while you keep the key pressed
down.
7. Save the parameter value by pressing .
Enter the rest of the motor data:
• nominal motor current (parameter 9906)
Allowed range: 0.2…2.0 · I
2N
A
• nominal motor frequency (parameter 9907)
• nominal motor speed (parameter 9908)
• nominal motor power (parameter 9909)
Select the application macro (parameter 9902)
according to how the control cables are
connected. The default value 1 (ABB
STANDARD) is suitable in most cases.