Advant Controller 450 Product Guide
Chapter 6 Technical Data and Performance
6-8 3BSE 015 953R201 Rev B
6.6 Time Synchronization
Between nodes on the same MasterBus 300/300E control network, the accuracy
is better than 3 ms.
External minute pulse can be connected to Advant Controller 450, giving an accuracy better
than 2 ms. between the external clock and the internal clock in Advant Controller 450.
6.7 Time Tagging of Events (Alarms)
S100 I/O or S800 I/O
Time tagging of two DI signals on S100 I/O boards or two DI signals on S800 I/O modules.
The relative time error between events handled within one controller is max. 2 ms.
The relative time error between events handled within separate controllers are max. 4 ms,
typically 3 ms.
S100 I/O and S800 I/O
Time tagging of one DI signal on S100 I/O board and one DI signal on S800 I/O module.
The relative time error between events handled within one controller is max. 3 ms.
The relative time error between events handled within separate controllers are max. 5 ms,
typically 4 ms.
S800 I/O
Time tagging in the controller system software.
For S800 I/O the relative time error between events (DI signals) in one controller can be
evaluated from the expression: Relative time error = a + b + c
a = scan cycle time of the FCI unit (5 - 100 ms, due to number of modules and types)
b = transmission cycle time of Advant Fieldbus 100 (set by the user)
c = scan cycle time of the PDC in Advant Controller 450 (set by the user)
Advant Controller 55/70/110/160
Time tagging in a controller Advant Controller 55/70/110/160. It is possible to receive events
from Advant Controller 70/110/160 using Advant Fieldbus 100, or from Advant Controller
55/110/160 using RCOM/RCOM+.

Table of Contents

Other manuals for ABB Advant Controller 450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Advant Controller 450 and is the answer not in the manual?

ABB Advant Controller 450 Specifications

General IconGeneral
BrandABB
ModelAdvant Controller 450
CategoryController
LanguageEnglish

Related product manuals