7.9 Application settings
In table 7.4 the recommended parameter settings for different applications are
described.
Table 7.4: Application settings
Recommended basic setting
Centrifugal fan 10 s OFF 40 % 5.0 x I
e
OFF OFF
Axial fan 10 s OFF 40 % 5.0 x I
e
OFF OFF
Centrifugal
pump
10 s 10 s 40 % 5.0 x I
e
OFF On
High pressure
pump
10 s 10 s 50 % 5.5 x I
e
OFF On
Compressor 5 s OFF 40 % 4.5 x I
e
OFF OFF
Grinder 10 s OFF 40 % 5.0 x I
e
OFF OFF
Mixer 10 s OFF 40 % 5.0 x I
e
OFF OFF
Bow thruster 10 s OFF 40 % 4.5 x I
e
OFF OFF
Hydraulic pump 10 s OFF 40 % 4.5 x I
e
OFF OFF
Crusher 10 s OFF 40 % 5.0 x I
e
OFF OFF
Conveyor belt 10 s OFF 50 % 5.0 x I
e
OFF OFF
Escalator 10 s OFF 40 % 4.5 x I
e
OFF OFF
Lift/Elevator 10 s OFF 40 % 4.5 x I
e
OFF OFF
Cutter 10 s OFF 40 % 5.0 x I
e
OFF OFF
Band saw 10 s OFF 40 % 5.0 x I
e
OFF OFF
Circular saw 10 s OFF 40 % 5.0 x I
e
OFF OFF
Please note that the parameter values above are to be used as a guide only. Variations in load
conditions may require additional tuning.
For Heavy Duty applications the Initial/End Voltage
as well as the Current Limit
might need to be increased.