KNX control elements and application parameters
Application "Scene actuator"
Product manual 2CKA00xx73xxxxx
193
10.20.6 Object type x
Options: Switch
Roller blind
Forced operation
1-byte value [0 - 100%]
1-byte value [0 - 255]
RGB colour
8-bit scene
RTC operating mode
Temperature
14-byte text
When actuated or during a sequence, components of a scene can send telegrams via the
associated communication object. Parameter "Object type x" is used to specify the size of the
communication object.
Switch: Switching commands are sent with 1 bit (0 or 1), e.g. for switching a switching
actuator. The following supplementary parameter is available:
Value for object x:
Options: OFF
ON
Notice
Parameter "Value for object x" can only be set for all options if parameter
"Object x is to be changed" is set on "Yes".
Roller blind: Allocation of a blind actuator. The following supplementary parameter is
available:
Value for object x:
Options: "Up/Open"
"Down/Close"
Forced operation: Management systems can access the device directly via KNX. It can
additionally be specified that selection can be carried out manually via buttons (forced
operation). The following supplementary parameter is available:
Value for object x:
Options: ON, forced operation active
OFF, forced operation active
Deactivate forced operation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SmartTouch i-bus KNX and is the answer not in the manual?

ABB SmartTouch i-bus KNX Specifications

General IconGeneral
BrandABB
ModelSmartTouch i-bus KNX
CategoryTouch Panel
LanguageEnglish

Related product manuals