KNX control elements and application parameters
Application "Internal RTC"
Product manual 2CKA00xx73xxxxx
226
10.24.44 Temperature reading — Control value for fault (0 - 255)
Options: Setting option between 0 - 255
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently determine the control value. In case of an error, a PWM control (1 Bit)
with a fixed cycle time of 15 minutes is used automatically instead of a parameterized 2-point
control (1 Bit). In this case the set parameter value is taken into consideration for the control
value during an error.