EasyManuals Logo
Home>Allen-Bradley>DC Drives>PowerFlex

Allen-Bradley PowerFlex User Manual

Allen-Bradley PowerFlex
235 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
2-102 Output Frequency
By using an output reactor the effective motor voltage will be lower because
of the voltage drop across the reactor - this may also mean a reduction of
motor torque.
Output Frequency [Output Frequency]
This parameter displays the actual output frequency of the drive. The output
frequency is created by a summation of commanded frequency and any
active speed regulator such as slip compensation, PI Loop, bus regulator.
The actual output may be different than the commanded frequency.
Output Power This parameter displays the output kW of the drive. The ouput power is a
calculated value and tends to be inaccurate at lower speeds. It is not
recommended for use as a process variable to control a process.
Output Voltage [Output Voltage]
This parameter displays the actual output voltage at the drive output
terminals. The actual output voltage may be different than that determined
by the sensorless vector or V/Hz algorithms because it may be modified by
features such as the Auto-Economizer.

Table of Contents

Other manuals for Allen-Bradley PowerFlex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex and is the answer not in the manual?

Allen-Bradley PowerFlex Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex
CategoryDC Drives
LanguageEnglish

Related product manuals