2-24 Auto Restart (Reset/Run)
Auto Restart (Reset/
Run)
The Auto Restart feature provides the ability for the drive to automatically
perform a fault reset followed by a start attempt without user or application
intervention. This allows remote or “unattended” operation. Only certain
faults are allowed to be reset. Certain faults (Type 2) that indicate possible
drive component malfunction are not resettable.
Caution should be used when enabling this feature, since the drive will
attempt to issue its own start command based on user selected
programming.
Conguration
This feature is configured through two user parameters
Setting [Auto Rstrt Tries] to a value greater than zero will enable the Auto
Restart feature. Setting the number of tries equal to zero will disable the
feature.
The [Auto Rstrt Delay] parameter sets the time, in seconds, between each
reset/run attempt.
The auto-reset/run feature provides 2 status bits in [Drive Status 2] – an
active status, and a countdown status.
The typical steps performed in an Auto-Reset/Run cycle are as follows:
1. The drive is running and an auto-resettable fault occurs, tripping the
drive.
2. After the number of seconds in [Auto Rstrt Delay], the drive will
automatically perform an internal Fault Reset, resetting the faulted
condition.
174 [Auto Rstrt Tries]
Sets the maximum number of times the
drive attempts to reset a fault and restart.
Default:
Min/Max:
Display:
0
0/9
1
175
175 [Auto Rstrt Delay]
Sets the time between restart attempts
when [Auto Rstrt Tries] is set to a value
other than zero.
Default:
Min/Max:
Display:
1.0 Secs
0.5/30.0 Secs
0.1 Secs
174
UTILITY
Diagnostics
210 [Drive Status 2]
Present operating condition of the drive.
Read Only 209
ATTENTION: Equipment damage and/or personal injury may result
if this parameter is used in an inappropriate application. Do Not use
this function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.
!
0000000x000000xx
10 01234567891112131415
1=Condition True
0=Condition False
x =Reserved
Bit #
R
eady
A
ctive
R
u
n
n
in
g
Jo
gg
in
g
S
to
pp
in
g
D
C
B
rakin
g
A
u
to
T
u
n
in
g
A
u
to
R
st C
td
n
A
u
to
R
st A
ct
C
u
rr L
im
it
B
u
s F
req
R
eg
M
o
to
r O
verld
D
P
I at 500 k

Table of Contents

Other manuals for Allen-Bradley PowerFlex

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex and is the answer not in the manual?

Allen-Bradley PowerFlex Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex
CategoryDC Drives
LanguageEnglish

Related product manuals