Digital Inputs 2-47
The available functions are defined in Table 2.K.
INPUTS & OUTPUTS
Digital Inputs
361
362
363
364
365
366
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
Selects the function for the digital inputs.
(1)
When [Digital Inx Sel] is set to option 2
“Clear Faults” the Stop button cannot
be used to clear a fault condition.
(2)
Typical 3-Wire Inputs.
Requires that only 3-wire functionsare
chosen. Including 2-wireselections will
cause a type 2 alarm.
(3)
Typical 2-Wire Inputs.
Requires that only 2-wire functionsare
chosen. Including 3-wireselections will
cause a type 2 alarm.
(4)
Speed Select Inputs.
To access Preset Speed 1, set [Speed
Ref A Sel] or [Speed Ref B Sel] to
“Preset Speed 1”.
Type 2 Alarms
Some digital input programming may
cause conflicts that will result in aType
2 alarm. For example, [Digital In1 Sel]
set to 5 “Start” in 3-wire control and
[Digital In2 Sel] set to 7 “Run” in 2-wire
control.
Refer to Alarm Descriptions on
page 4-8 for information on resolving
this type of conflict.
(5)
Auto/Manual - Refer to Figure 1.6 on
page 1-13 for details.
Default:
Default:
Default:
Default:
Default:
Default:
Options:
4
5
10
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
“Stop – CF”
(CF = Clear Fault)
“Start”
“Jog”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Not Used”
“Enable”
“Clear Faults”
(1)
“Aux Fault’
“Stop – CF”
(2)
“Start”
(2)
“Fwd/ Reverse”
(2)
“Run”
(3)
“Run Forward”
(3)
“Run Reverse”
(3)
“Jog”
(2)
“Jog Forward”
“Jog Reverse”
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1”
(4)
“Speed Sel 2”
(4)
“Speed Sel 3”
(4)
“Auto/ Manual”
(5)
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
“Precharge En”
100
156
162
096
140
194
380
124
321AutoReference Source
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7