Troubleshooting SiBE12-908
121 Service Diagnosis
2.8 Freeze-up Protection Control or Heating Peak-cut Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
Heating peak-cut control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
Freeze-up protection control (operation halt) is activated during cooling operation according
to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
Heating peak-cut control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.

Table of Contents

Other manuals for Daikin 2MXU40GV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXU40GV1B and is the answer not in the manual?

Daikin 2MXU40GV1B Specifications

General IconGeneral
BrandDaikin
Model2MXU40GV1B
CategoryHeat Pump
LanguageEnglish

Related product manuals