Troubleshooting SiBE12-908
127 Service Diagnosis
2.12 Signal Transmission Error (Indoor Unit - Outdoor Unit)
Remote
Controller Display
U4
Method of
Malfunction
Detection
The data sent from the outdoor unit is checked for problem.
Malfunction
Decision
Conditions
When the data sent from the outdoor unit can not be received without error, or when the disable
status of signal transmission continues for 15 seconds.
Supposed
Causes
Defective outdoor unit PCB
Defective indoor unit PCB
Signal transmission error between indoor and outdoor unit due to improper wiring
Signal transmission error between indoor and outdoor unit due to breakage of relay wire
(transmission wire)