Check SiBE12-908
175 Service Diagnosis
3.10 Discharge Pressure Check
Check No.16
(R9683)
Discharge pressure check
YES
NO
Is it high?
NO
YES
YES
NO
NO
YES
Is the stop valve open?
Is the connection pipe
deformed?
Are the heat exchanger
and air filter dirty?
Replace the compressor.
Open the stop valve.
Replace the field piping.
Clean it.
Replace the compressor.