Table 14: Technical Data for VACON® 1000
Multilevel IGBT topology (Cascade H-Bridge)
Voltage source inverter (VSI)
Pulse-width modulated (PWM) power modules
-10%...+10% (normal operation)
-10%...-30% (derated continuous operation)
50/60 Hz (±5% transients)
±10% of nominal, unbalance up to 3% per IEC 610002-4
-30% of nominal without tripping
Continuous operation with reduced power, derated power 70–90%.
Short-circuit current rating
(SCCR)
Control voltage with circuit
protection
1-phase 230 V AC, 50 Hz
1-phase 220 V AC, 60 Hz
1-phase AC 120–240 V
3-phase AC 240–480 V
Capacity 5 kVA (other voltages available)
Meets IEEE 519 standard, without input filter
Multiphase isolation transformer integrated into the drive
Transformer type of construc-
tion
Dry type, phase shifting, Cu/Cu; Forced air cooling
Al/Cu or Al/Al available as an engineered option.
Transformer insulation type
Transformer inrush current
limitation
I
n
>215 A limited with start-up cabinet (optional, +PSTC)
Transformer secondary for
auxiliaries
3-phase, 460 V AC with neutral and with a 380 V AC tap, 50/60 Hz
Temperature sensors in trans-
former windings
3x PT100, one in each winding
Tin-plated grounding busbar section
Output current THDi (1st…
49th)