EasyManuals Logo
Home>Danfoss>Media Converter>VACON 1000

Danfoss VACON 1000 User Manual

Danfoss VACON 1000
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
>2000 m (on request)
Chemical environment condi-
tions
IEC 60721-3-3: Class 3C2
Environment corrosion cate-
gory
According to ISO/EN 12944-2: C1 as default; C4 as an engineered op-
tion
Electromagnetic compatibili-
ty environment
IEC 61000-2-5: Industrial
Seismic zone/Ground acceler-
ation
Zone 2 (standard)
Zone 4 (optional, +SZ04)
System burn-in at factory be-
fore delivery
4 h minimum, according to IEEE 1566
ATEX area: Flammable prod-
uct/Zone
IEC 60079-10-1/2: as an engineered option, certified per EN
50495:2010
Noise level
≤85 dB(A) at 1 m from the enclosure
Structure
Dimension and weight
See 11.2 Power Ratings and Dimensions.
Cabinet sheet metal thickness
Doors and panels: 1.5 mm
Base: 5 mm
Cable entry
Input, motor, and control cables: Bottom and top
Cooling system
Type
Forced air cooling including fan monitoring.
Fan redundancy available as option, +QDFR.
External auxiliary AC voltage
for cooling fans (optional,
+QDEX)
380–460 V AC, 50 Hz
380–460 V AC, 60 Hz
Protection level
IEC
IP31 (standard)
IP42 (optional, +IP42)
UL
NEMA 1
Auxiliaries
Cabinet lights
In the control cabinet
Power cell bypass
Automatic via IGBT, 1 ms bypass time (optional, +PPCB)
UPS for control voltage (DC)
30 min running time
11.2 Power Ratings and Dimensions
11.2.1 IEC Ratings
AQ363633621020en-000201 / 172F3117 | 111Danfoss A/S © 2021.06
Specifications
VACON® 1000
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VACON 1000 and is the answer not in the manual?

Danfoss VACON 1000 Specifications

General IconGeneral
BrandDanfoss
ModelVACON 1000
CategoryMedia Converter
LanguageEnglish

Related product manuals