1.
Check the heater and humidistat. Set the threshold of the humidistat below the ambient hu-
midity and check that the heater starts working. After testing, set the threshold to 80%.
Check the high voltage electric display light and that the second locked circuit is normal.
Check that the thermal relay setting value is correct.
Do a close test for the vacuum contactor or breaker, and check that the operation and feed-
back status is correct.
Check that the fuse and breaker is normal and there are no burn marks.
Change the battery every 3 years for reliable operation.
If the drive is stored for over 3 months and is not turned on during that time, charge the UPS
battery for 8 hours.
Charge spare storage batteries every 3 months.
The brightness of the HMI decays over time. The lifetime depends on the use conditions.
High voltage
electric display
device
Change every 4 years for reliable operation.
If a stored power cell has not been energized in the last 1 year, the electrolytic capacitors
must be reformed.
If the drive is stored for more than 2 years, high voltage cannot be applied directly to the
drive. Raise the input voltage gradually to wait until the capacitors are charged properly.
9.4 Replacing the Air Filters
9.4.1 Air Filters of Standalone Cabinets
Procedure
Loosen the screws on the air filter cover.
Illustration 69: Releasing the Filter Cover
AQ363633621020en-000201 / 172F311782 | Danfoss A/S © 2021.06
Maintenance