0-04 Operating State at Power-up
Select the operating mode after reconnection of the frequency
converter to mains voltage after power-down when operating in
Hand (local) mode.
Option: Function:
[0] * Resume Resumes operation of the
frequency converter, maintaining
the same local reference and the
same start/stop condition (applied
by [Hand On]/[O] on the LCP or
local start via a digital input) as
before the frequency converter was
powered down.
[1] Forced stop,
ref=old
Uses saved reference [1] to stop the
frequency converter, but at the
same time retains the local speed
reference in memory before
powering down. After mains
voltage is reconnected, and after
receiving a start command
(pressing [Hand On] key or using
the local start command via a
digital input), the frequency
converter restarts and operates at
the retained speed reference.
0-06 GridType
Select the grid type of the supply voltage/frequency.
IT grid is a supply mains, where there are no connections to
ground.
Delta is a supply mains where the secondary part of the
transformer is delta connected and one phase is connected to
ground.
Option: Function:
NOTICE
Not all options are supported
in all power sizes.
[0] 200-240V/
50Hz/IT-grid
[1] 200-240V/
50Hz/Delta
[2] 200-240V/
50Hz
[10] 380-440V/
50Hz/IT-grid
[11] 380-440V/
50Hz/Delta
[12] 380-440V/
50Hz
[20] 440-480V/
50Hz/IT-grid
[21] 440-480V/
50Hz/Delta
[22] 440-480V/
50Hz
[30] 525-600V/
50Hz/IT-grid
[31] 525-600V/
50Hz/Delta
[32] 525-600V/
50Hz
[100] 200-240V/
60Hz/IT-grid
[101] 200-240V/
60Hz/Delta
[102] 200-240V/
60Hz
[110] 380-440V/
60Hz/IT-grid
[111] 380-440V/
60Hz/Delta
[112] 380-440V/
60Hz
[120] 440-480V/
60Hz/IT-grid