EasyManuals Logo
Home>Danfoss>DC Drives>VLT CDS 803

Danfoss VLT CDS 803 Programming Guide

Danfoss VLT CDS 803
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
Input) to [32] Pulse input. If terminal 29 is used as an input,
set parameter 5-01 Terminal 27 Mode to [0] Input.
130BA076.10
(RPM)
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 3.7 Pulse Input
5-50 Term. 29 Low Frequency
Range: Function:
20 Hz* [20 - 31999
Hz]
Enter the low frequency limit
corresponding to the low
compressor shaft speed (that is, low
reference value) in
parameter 5-52 Term. 29 Low Ref./
Feedb. Value. See Illustration 3.7.
5-51 Term. 29 High Frequency
Range: Function:
32000 Hz* [21 - 32000
Hz]
Enter the high frequency limit
corresponding to the high
compressor shaft speed (that is,
high reference value) in
parameter 5-53 Term. 29 High Ref./
Feedb. Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the low reference value limit
for the compressor shaft speed
[RPM]. This is also the lowest
feedback value. Set terminal 29 to
digital input.
5-53 Term. 29 High Ref./Feedb. Value
Range: Function:
Size
related*
[-4999 -
4999 ]
Enter the high reference value
[RPM] for the compressor shaft
speed and the high feedback value.
Select terminal 29 as a digital input.
3.6.5 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
eldbus setting.
5-90 Digital & Relay Bus Control
This parameter holds the state of the buscontrolled digital
outputs and relays.
Range: Function:
0* [0 -
0xFFFFFFFF ]
A logical 1 indicates that the
output is high or active. A logical 0
indicates that the output is low or
inactive.
Bit 0-3 Reserved
Bit 4 Relay 1 output terminal
Bit 6-23 Reserved
Bit 24 Terminal 42 digital output
Bit 26-31 Reserved
Table 3.4 Bit Functions
3.7 Main Menu - Analog In/Out - Group 6
Parameter group for setting up the analog I/O congu-
ration and the digital output.
The frequency converter provides 2 analog inputs:
Terminal 53.
Terminal 54.
The analog inputs can be freely allocated to either voltage
(0–10 V) or current input (0/4–20 mA).
3.7.1 6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
Range: Function:
10 s* [1 - 99 s] Enter the timeout time.
6-01 Live Zero Timeout Function
Select the timeout function. The function set in
parameter 6-01 Live Zero Timeout Function is activated if the input
signal on terminal 53 or 54 is below 50% of the value in
parameter 6-10 Terminal 53 Low Voltage, parameter 6-12 Terminal
53 Low Current, parameter 6-20 Terminal 54 Low Voltage, or
parameter 6-22 Terminal 54 Low Current for a time period dened
in parameter 6-00 Live Zero Timeout Time.
Option: Function:
[0] * O
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
Parameters Programming Guide
MG18P202 Danfoss A/S © 06/2019 All rights reserved. 35
3 3

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals