Control card, 24 V DC output
Terminal number 13
Output voltage 24 V (+1, -3 v)
Max. load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs 2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (resistive load) 240 V AC, 2A
Max. terminal load (AC-15)
1)
(inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (resistive load) 60 V DC, 1 A
Max. terminal load (DC-13)
1)
(inductive load) 24 V DC, 0.1 A
Relay 02 Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (resistive load)
2)3)
400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (inductive load) 24 V DC, 0.1 A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (inductive load) 24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300 V AC 2 A
Control characteristics
Resolution of output frequency at 0-1000 Hz ±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33) 2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed accuracy (open loop) 30-4000 RPM: Maximum error of ±8 RPM
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure, frame size D and E IP21, IP54
Enclosure, frame size F IP21, IP54
Vibration test 0.7 g
Relative humidity 5-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class kD
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating max. 55 °C
- with full output power, typical IE2 motors (see chapter 11.1.2 Derating for Temperature max. 50 °C
- at full continuous FC output current max. 45 °C
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level without derating 1,000 m
Maximum altitude above sea level with derating 3,000 m
For more information on derating, consult the design guide
EMC standards, emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
Specifications Operating Instructions
148 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202
1111

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 302 and is the answer not in the manual?

Danfoss VLT FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 302
CategoryController
LanguageEnglish

Related product manuals