68 Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
77..11..11 CChhaannggiinngg tthhee LLaanngguuaaggee
Press and hold the first button on the left for approximately five seconds to select the language menu. This
action is possible from any LCD menu screen.
77..11..22 DDiissppllaayy FFuunnccttiioonnss
As the default or after 15 minutes of inactivity, the LCD displays the selectable startup screen. The default is
the Eaton logo and can be changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press any button to restore the screen.
Use the two middle buttons (
and ) to scroll through the menu structure. Press the button to enter a
submenu. Press the
button to select an option. Press the
button to cancel or return to the
previous menu.
The following table shows the basic menu structure.
Table 9. Menu Map for Display Functions
Main Menu Submenu
Display Information or Menu Function
UPS Status UPS off / System normal / UPS supporting load / UPS on battery / UPS on bypass /
Active alarm list / Battery status
Event Log Displays up to 127 events and alarms
Measurements
Output L-N and L-L / Current / Frequency / Power
Battery Voltage / Current / Runtime
Input L-N and L-L / Current / Frequency
Bypass L-N and L-L / Frequency
Control Go to Bypass Mode Transfers the UPS to internal Bypass mode
When this command is active, the option changes to Go to Normal Mode.
Start Battery Test Initiates a battery test
Display Test Four different selectable tests for the front panel functions: the LEDs cycle through,
the alarm beep sounds, the backlight turns off and on, and the pixels scroll through
to test the LCD.
Settings User Settings See Table 10 for more information.
Service Settings This screen is password-protected.
Identification UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge
Turn UPS ON/OFF ON and OFF Options
77..11..33 UUsseerr SSeettttiinnggss
The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning on
the UPS; otherwise, the changes do not take effect.
UPS Operating Instructions