EasyManuals Logo

Eaton 9155 UPS User Manual

Eaton 9155 UPS
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #82 background imageLoading...
Page #82 background image
74 Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
Figure 52. Maintenance Bypass Switch
NOTE: PDM shown
The UPS-mounted bypass switch has three positions as described in Table 11.
NOTE In the UPS or SERVICE position, AC input power is still connected to the input terminals
inside the UPS.
Table 11. UPS-Mounted Bypass Switch Positions
Switch Position Description
UPS Connects the UPS output to the load.
SERVICE Connects the load directly to AC input power and disconnects UPS output. AC input power is still connected
to the UPS input.
BYPASS Like the SERVICE position, BYPASS connects the load directly to AC input power and disconnects UPS
output. However, because BYPASS also disconnects AC input from the UPS, this is the appropriate position
for UPS maintenance or repair.
Figure 53 shows a UPS with a separate battery cabinet and a UPS-mounted bypass switch.
UPS Operating Instructions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9155 UPS and is the answer not in the manual?

Eaton 9155 UPS Specifications

General IconGeneral
Input Frequency50/60 Hz
Output Frequency50/60 Hz
Operating Temperature0°C to 40°C (32°F to 104°F)
Humidity0-95% non-condensing
DimensionsVaries by model
WeightVaries by model
Communication PortsUSB
Safety ApprovalsUL, cUL, CE
Output Voltage208/220/230/240 VAC
Battery TypeValve-regulated lead acid (VRLA)
Storage Temperature-15°C to 45°C (5°F to 113°F)

Related product manuals