Electrical Installation
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerquality 31
Options Cabinet with Dual-Feed Wiring
To hardwire the Options Cabinets in a dual-feed system:
1. Remove the Options Cabinet conduit landing box from both Options Cabinet rear panels and retain (see
Figure 19 on page 29).
2. Punch two holes in the first conduit landing box for the input and output conduit using a Greenlee punch or
similar device.
Punch one hole in the second conduit landing box for the second input conduit.
3. Route the wiring from the back of the first Options Cabinet, through the wiring tray, to the front of the
Options Cabinet.
Route the wiring from the back of the second Options Cabinet, through the wiring tray, to the front of the
Options Cabinet.
4. On the first Options Cabinet, hardwire the input, output, and ground terminations. See Table 1 on page 35
for wiring specifications.
On the second Options Cabinet, hardwire the second input and ground terminations.
For a detailed view of both Options Cabinet terminal blocks, see Figure 21.
5. Remove the jumpers between the UPS input terminal block and the input circuit breaker (see Figure 23 on
page 36).
6. On the first Options Cabinet, route the factory-installed wiring through the knockouts and hardwire to the
UPS terminal block.
On the second Options Cabinet, route the factory-installed wiring through the knockouts and hardwire to
the UPS input circuit breaker.
For a detailed view of the UPS terminal block, see Figure 23 on page 36.
7. On the first Options Cabinet, route the maintenance bypass auxiliary wiring through the knockouts to the
UPS and wire to the contacts below the MBS (see Figure 21).
8. Reinstall both Options Cabinet wiring access covers.
9. Reinstall both Options Cabinet conduit landing boxes in the reversed position (see Figure 19 on page 29).
10. Replace both Options Cabinet front doors (see page 10).
11. Reinstall the UPS connections insulator.
12. Reinstall the UPS wiring access cover.
13. Replace the UPS front door (see page 10).

Table of Contents

Other manuals for Eaton 9355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9355 and is the answer not in the manual?

Eaton 9355 Specifications

General IconGeneral
Efficiency91 %
Noise level58 dB
Output power27000 W
Input frequency50/60 Hz
Audible alarm(s)Yes
Input power factor0.99
Output power factor0.9
Output power capacity30 kVA
Input operation voltage (min)220 V
Input current Total Harmonic Distortion (THD)5 %
RS-232 ports1
AC outlet types-
AC outlets quantity- AC outlet(s)
SafetyIEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778, NOM-0190SCP8-1993
Form factorTower
Display typeLCD
CertificationEN 50091-2 Class A\\r UL, cUL, NOM-NYCE
Product colorBlack
Battery technologySealed Lead Acid (VRLA)
Typical backup time at half load- min
Operating altitude0 - 3000 m
Storage temperature (T-T)0 - 25 °C
Operating temperature (T-T)10 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Depth866.14 mm
Width508 mm
Height1676.4 mm