EasyManuals Logo

Eaton 9355 Installation And Operation Manual

Eaton 9355
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Electrical Installation
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerquality 33
Options Cabinet with Output Transformer Wiring
To hardwire the Options Cabinets for 480V loads:
1. Remove the Options Cabinet conduit landing box from both Options Cabinet rear panels and retain (see
Figure 19 on page 29).
2. Punch one hole in the first conduit landing box for the input conduit using a Greenlee punch or similar
device.
Punch one hole in the second conduit landing box for the output conduit.
3. Route the wiring from the back of the first Options Cabinet, through the wiring tray, to the front of the
Options Cabinet.
Route the wiring from the back of the second Options Cabinet, through the wiring tray, to the front of the
Options Cabinet.
4. On the first Options Cabinet, hardwire the input and ground terminations. See Table 1 on page 35 for
wiring specifications.
On the second Options Cabinet, hardwire the output and ground terminations.
For a detailed view of both Options Cabinet terminal blocks, see Figure 22.
5. On the second Options Cabinet, route the factory-installed wiring through the knockouts and hardwire to
the output terminal block of the first Options Cabinet.
On the first Options Cabinet, route the factory-installed wiring through the knockouts and hardwire to the
UPS terminal block.
For a detailed view of the UPS terminal block, see Figure 23 on page 36.
6. On the first Options Cabinet, route the maintenance bypass auxiliary wiring through the knockouts to the
UPS and wire to the contacts below the MBS (see Figure 22).
7. Reinstall both Options Cabinet wiring access covers.
8. Reinstall both Options Cabinet conduit landing boxes in the reversed position (see Figure 19 on page 29).
9. Replace both Options Cabinet front doors (see page 10).
10. Reinstall the UPS connections insulator.
11. Reinstall the UPS wiring access cover.
12. Replace the UPS front door (see page 10).

Table of Contents

Other manuals for Eaton 9355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9355 and is the answer not in the manual?

Eaton 9355 Specifications

General IconGeneral
Efficiency91 %
Noise level58 dB
Output power27000 W
Input frequency50/60 Hz
Audible alarm(s)Yes
Input power factor0.99
Output power factor0.9
Output power capacity30 kVA
Input operation voltage (min)220 V
Input current Total Harmonic Distortion (THD)5 %
RS-232 ports1
AC outlet types-
AC outlets quantity- AC outlet(s)
SafetyIEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778, NOM-0190SCP8-1993
Form factorTower
Display typeLCD
CertificationEN 50091-2 Class A\\r UL, cUL, NOM-NYCE
Product colorBlack
Battery technologySealed Lead Acid (VRLA)
Typical backup time at half load- min
Operating altitude0 - 3000 m
Storage temperature (T-T)0 - 25 °C
Operating temperature (T-T)10 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Depth866.14 mm
Width508 mm
Height1676.4 mm

Related product manuals