EasyManuals Logo

Eaton 9355 Installation And Operation Manual

Eaton 9355
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
UPS Maintenance
82 Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F www.eaton.com/powerquality
Parallel UPS Bypass
To switch the parallel UPS to maintenance bypass from Normal mode:
Note: All UPSs go to bypass using the following procedure.
1. From any UPS, set the system to internal Bypass mode:
l
Using the button on the front panel display, scroll to the Control menu option and press the button.
l
Press the button to select the Go to Bypass Mode option.
The indicator illuminates and the indicator extinguishes, indicating the UPS system is operating
in Bypass mode.
2. Switch the bypass breaker on the Tie Cabinet to the ON position.
3. If present, switch the maintenance isolation breaker on the Tie Cabinet to the OFF position; otherwise,
switch the UPS breakers on the Tie Cabinet to the OFF position.
The UPS is now bypassed, with the load powered by utility power.
To return the parallel UPS to Normal mode from maintenance bypass:
1. Verify that the maintenance isolation breaker (if present) on the Tie Cabinet is in the off position or all of
the UPS breakers are in the OFF position.
2. Switch on utility power where the UPSs are connected.
In a parallel capacity system (N+0 or N+1), apply utility to the minimum number of UPSs required for
capacity.
The indicator illuminates, indicating the UPS system is operating in Bypass mode.
Note: Use the same UPS that was used to set internal bypass to return the parallel system to Normal
mode.
3. If present, switch the maintenance isolation breaker on the Tie Cabinet to the ON position; otherwise,
switch all UPS breakers to the ON position.
4. Switch the bypass breaker on the Tie Cabinet to the OFF position.
5. On the same UPS front panel, set the UPS to Normal mode:
l
Press the button to select the Go to Normal Mode option.
l
Each UPS should go to Normal mode.
The UPS is now powering the load in Normal mode.

Table of Contents

Other manuals for Eaton 9355

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9355 and is the answer not in the manual?

Eaton 9355 Specifications

General IconGeneral
Efficiency91 %
Noise level58 dB
Output power27000 W
Input frequency50/60 Hz
Audible alarm(s)Yes
Input power factor0.99
Output power factor0.9
Output power capacity30 kVA
Input operation voltage (min)220 V
Input current Total Harmonic Distortion (THD)5 %
RS-232 ports1
AC outlet types-
AC outlets quantity- AC outlet(s)
SafetyIEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778, NOM-0190SCP8-1993
Form factorTower
Display typeLCD
CertificationEN 50091-2 Class A\\r UL, cUL, NOM-NYCE
Product colorBlack
Battery technologySealed Lead Acid (VRLA)
Typical backup time at half load- min
Operating altitude0 - 3000 m
Storage temperature (T-T)0 - 25 °C
Operating temperature (T-T)10 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Depth866.14 mm
Width508 mm
Height1676.4 mm

Related product manuals