DTP COMP STOP: Error Indication
Protection controlling range in Cooling mode
R
S
R
S
S
R
DTP2: Outdoor unit rotation excution
DTP3: limited Compressor speed
F
controlling
DTP1: EEV3 Liquid injection controlling
176 194 203 212 221 225 239 ( )
Note:
Target pressure controlling will be cancelled when the temperature is in the range color orange.
R
S
DTP COMP STOP: Error Indication
Protection controlling range in Heating mode
R
S
R
S
DTP3: limited Compressor speed
controlling
DTP1: EEV3 Liquid injection controlling
DTP5: EEV1,EEV2 opening controlling
R
S
176
194 203 212 216 221 239 ( )
S
R
DTP4: Indoor unit EEV opening
controlling
Note:
Target pressure controlling will be cancelled when the temperature is in the range of orange.
F
Discharge temperature protection -Summary-
185
02-17
C
80 90 95 100 105 107 115 ( )
80
90 95 97 100 102 105 115 ( )
C
85
207