EasyManuals Logo
Home>GE>Control Unit>MiCOM P142 Agile

GE MiCOM P142 Agile User Manual

GE MiCOM P142 Agile
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #148 background imageLoading...
Page #148 background image
Note:
Although the start point of the charact
eristic is defined by the "ΙN>" setting, the actual current threshold is a different setting
called "IDG Ιs". The "IDG Ιs" setting is set as a multiple of "ΙN>".
Note:
When using an IDG Operate charact
eristic, DT is always used with a value of zero for the Rest characteristic.
An additional setting "IDG Time" is also used to set the minimum operating time at high levels of fault current.
0
1
2
3
4
5
6
7
8
9
10
1 10 100
I/IN>
Operating time (seconds)
IDG Is Setting Range
IDG Time Setting Range
V00611
IDG Time Setting Range
IDG Is Setting Range
O
p
e
r
a
t
i
n
g
t
i
m
e
(
s
e
c
o
n
d
s
)
Figure 49: IDG Characteristic
10.4 DIRECTIONAL ELEMENT
If Earth fault current can flow in both directions through a protected location, you will need to use a directional
over
current element to determine the direction of the fault. Typical systems that require such protection are
parallel feeders and ring main systems.
A directional element is available for all of the Earth Fault stages. These are found in the direction setting cells for
the relevant stage. They can be set to non-directional, directional forward, or directional reverse.
Directional control can be blocked by the VTS element if required.
For standard earth fault protection, two options are available for polarisation; Residual Voltage (zero sequence) or
Negative Sequence.
10.4.1 RESIDUAL VOLTAGE POLARISATION
With earth fault protection, the polarising signal needs to be representative of the earth fault condition. As residual
voltage is generated during ear
th fault conditions, this quantity is commonly used to polarise directional earth
fault elements. This is known as Zero Sequence Voltage polarisation, Residual Voltage polarisation or Neutral
Displacement Voltage (NVD) polarisation.
Small levels of residual voltage could be present under normal system conditions due to system imbalances, VT
inaccuracies, device tolerances etc. For this reason, the device includes a user settable threshold (IN> VNPol set),
which must be exceeded in order for the DEF function to become operational. The residual voltage measurement
provided in the MEASUREMENTS 1 column of the menu may assist in determining the required threshold setting
during the commissioning stage, as this will indicate the level of standing residual voltage present.
Chapter 6 - Current Protection Functions P14x
122 P14xEd1-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P142 Agile and is the answer not in the manual?

GE MiCOM P142 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P142 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals