13 ENVIRONMENTAL CONDITIONS
13.1 AMBIENT TEMPERATURE RANGE
Compliance IEC 60255-27: 2005
Test Method IEC 60068-2-1:2007 and IEC 60068-2-2 2007
Operating temperature range -25°C to +55°C (continuous)
Storage and transit temperature range -25°C to +70°C (continuous)
13.2 TEMPERATURE ENDURANCE TEST
Temperature Endurance Test
Test Method IEC 60068-2-1: 1993 and 60068-2-2: 2007
Operating temperature range
-40°C (96 hours)
+70°C (96 hours)
S
torage and transit temperature range
-40°C (96 hours)
+70°C (96 hours)
13.3 AMBIENT HUMIDITY RANGE
Compliance IEC 60068-2-78: 2001 and IEC 60068-2-30: 2005
Durability 56 days at 93% relative humidity and +40°C
Damp heat cyclic six (12 + 12) hour cycles, 93% RH, +25 to +55°C
13.4 CORROSIVE ENVIRONMENTS
Compliance IEC 60068-2-42: 2003, IEC 60068-2-43: 2003
Industrial corrosive environment/poor environmental
control, S
ulphur Dioxide
21 days exposure to elevated concentrations (25ppm) of SO
2
at
75% relativ
e humidity and +25°C
Industrial corrosive environment/poor environmental
contr
ol, Hy
drogen Sulphide
21 days exposure to elevated concentrations (10ppm) of H
2
S at
75% relativ
e humidity and +25°C
Salt mist IEC 60068-2-52: 1996 KB severity 3
Chapter 23 - Technical Specifications P14x
556 P14xEd1-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P142 Agile and is the answer not in the manual?

GE MiCOM P142 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P142 Agile
CategoryControl Unit
LanguageEnglish

Related product manuals