4.5 RATE OF CHANGE OF VOLTAGE PROTECTION
Accuracy for 110 V VT
Tolerance 1% or 0.07, whichever is greater
Pick-up Setting +/- tolerance
Drop-off for positive direction (Setting – 0.07)+/- tolerance
Drop-off for negative direction (Setting + 0.07)+/- tolerance
Operating time at 50 Hz (Average cycle x 20) +60 ms
Reset time at 50 Hz 40 ms
Chapter 23 - Technical Specifications P14x