EasyManuals Logo
Home>GW Instek>Portable Generator>ASR-2000 Series

GW Instek ASR-2000 Series Programming Manual

GW Instek ASR-2000 Series
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
ASR-2000 Programming Manual
100
[:SOURce]:SIMulation:INITial:PHASe:STOP
:ENABle
Set
Query
Description
Enables/Disables (Fixed/Free) the OFF Phs
parameter of the initial step for the Simulation mode.
Syntax
[:SOURce]:SIMulation:INITial:PHASe:STOP:ENABle
{<bool>|OFF|ON|FREE|FIXED }
Query Syntax
[:SOURce]:SIMulation:INITial:PHASe:STOP:ENABle?
Parameter/Return
parameter
OFF | 0 |
FREE
Disabled
ON | 1 |
FIXED
Enabled
Example
:SIM:INIT:PHAS:STOP:ENAB 1
Enable the OFF Phs.
[:SOURce]:SIMulation:INITial:PHASe:STOP
[:IMMediate]
Set
Query
Description
Sets or queries the OFF Phs parameter of the initial
step for the Simulation mode.
Note:
Sets the off phase of the waveform after the output
has been turned off.
Syntax
[:SOURce]:SIMulation:INITial:PHASe:STOP
[:IMMediate] {<NR2>|MINimum|MAXimum}
Query Syntax
[:SOURce]:SIMulation:INITial:PHASe:STOP
[:IMMediate]? [MINimum|MAXimum]
Parameter/Return
parameter
<NR2>
OFF Phs (Stop phase)
MINimum
0
MAXimum
359.9
Example
:SIM:INIT:PHAS:STOP 0
Sets OFF Phs to 0.

Table of Contents

Other manuals for GW Instek ASR-2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GW Instek ASR-2000 Series and is the answer not in the manual?

GW Instek ASR-2000 Series Specifications

General IconGeneral
BrandGW Instek
ModelASR-2000 Series
CategoryPortable Generator
LanguageEnglish

Related product manuals