36 UDACT Instruction Manual — P/N 50050:M 12/18/2009
Programming Instructions Programming Options
Any of the event codes may be changed. Consult your Central Station prior to altering the
event codes. For the 3+1, 4+1 and 4+1 Express formats, entering an event code of “0” will cause
the communicator to NOT transmit the report. Enter two zeroes for 4+2 and 4+2 Express Formats.
For Ademco Contact ID format enter three zeroes. Transmission of reports to either or both Central
Station phone numbers may be disabled.
Note the special “System Abnormal Test Report” event code. This report was added per UL DACT
requirements. This report is generated in place of the normal test report when an alarm and/or
trouble condition exists at the time the test report is due to be sent.
3.4.23 Programming the Real-Time Clock
Entering an address greater than 209 will cause a display of the current time. On power up, the
clock will start running from the factory setting of 00:01 (military time).
The far left digit will be flashing, indicating that this is the first digit to be programmed. Select a
digit then press
ENTER/STORE. The digit 2nd from the left will start flashing. Select a digit then
press
ENTER/STORE. Hours setting is complete. With the digit 2nd from the right flashing, select a
digit then press
ENTER/STORE. The digit on the far right will start flashing. Select a digit then press
ENTER/STORE. Minutes setting is complete.
3.4.24 End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code corresponding to an
alternate mode of operation, then press
ENTER/STORE. For example to return to Normal Mode: Press
MODE, 6676, and ENTER/STORE. During Program Mode, if no key is pressed within 10 minutes, the
UDACT will revert to Normal Mode.