38 UDACT Instruction Manual — P/N 50050:M 12/18/2009
Programming Instructions 3+1, 4+1 Express and 4+1 Standard Formats
3.5.2 Secondary Number
If “0”, “2”, “4”, “6” or “8” are entered for address 42, the following data is automatically
programmed for the secondary phone number event codes. Enter a “0” for the data setting to
disable the report. These formats do not support zone/point programming. For zone/point reporting,
refer to Contact ID.
Table 3.3 Event Codes, Secondary Number
Address Description Setting
139 Secondary # General Alarm Code 1
140 Secondary # Zone/Point Alarm Code 0
141 Secondary # General Supervisory Code 8
142 Secondary # Zone/Point Supervisory Code 0
143 Secondary # General Fault Code F
144 Secondary # AC Fault Code F
145 Secondary # Zone/Point Fault Code 0
146 Secondary # Low Battery Fault Code F
147 Secondary # Telco Primary Line Fault Code F
148 Secondary # Telco Secondary Line Fault Code F
149 Secondary # NAC Fault Code F
150 Secondary # Comm. Trouble Primary # Code F
151 Secondary # Comm. Trouble Secondary # Code F
152 Secondary # 485 Comm. Trouble Code F
153 Secondary # System Off Normal Code F
154 Secondary # UDACT Off Normal Code F
155 Secondary # General Alarm Restore Code E
156 Secondary # Zone/Point Alarm Restore Code 0
157 Secondary # General Supervisory Restore Code E
158 Secondary # Zone/Point Supervisory Restore Code 0
159 Secondary # General Fault Restore Code E
160 Secondary # AC Fault Restore Code E
161 Secondary # Zone/Point Fault Restore Code 0
162 Secondary # Low Battery Fault Restore Code E
163 Secondary # Telco Primary Line Fault Restore Code E
164 Secondary # Telco Secondary Line Fault Restore Code E
165 Secondary # NAC Fault Restore Code E
166 Secondary # Comm.Trouble Primary Number Restore Code E
167 Secondary # Comm. Trouble Secondary Number Restore Code E
168 Secondary # 485 Comm. Trouble Restore Code E
169 Secondary # System Off Normal Restore Code E
170 Secondary # UDACT Off Normal Restore Code E
171 Secondary # System 24 Hour Test 9
172 Secondary # System 24 Hour Test w/active event F
173 Secondary # Manual Test 9
NOTE: Zero entries prevent the transmission of the report to the Central Station.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals