40 UDACT Instruction Manual — P/N 50050:M 12/18/2009
Programming Instructions 4+2 Standard and 4+2 Express Formats
3.6.2 Secondary Number
If “1”, “A” or “C” are entered for address 42, the following data is automatically programmed for the
secondary phone number event codes. Enter a “0” for the data setting to disable the report. These
formats do not support zone/point programming. For zone/point reporting, refer to Contact ID.
Table 3.5 Event Codes, Secondary Number
Address Description Setting
139-140 Secondary# General Alarm Code 11
141-142 Secondary # Zone/Point Alarm Code 00
143-144 Secondary # General Supervisory Code 81
145-146 Secondary # Zone/Point Supervisory Code 00
147-148 Secondary # General Fault Code F1
149-150 Secondary # AC Fault Code F6
151-152 Secondary # Zone/Point Fault Code 00
153-154 Secondary # Low Battery Fault Code F8
155-156 Secondary # Telco Primary Line Fault Code FA
157-158 Secondary # Telco Secondary Line Fault Code FB
159-160 Secondary # NAC Fault Code FC
161-162 Secondary # Comm. Trouble Primary # Code FD
163-164 Secondary # Comm. Trouble Secondary # Code FE
165-166 Secondary # 485 Comm. Trouble Code FE
167-168 Secondary # System Off Normal Code FF
169-170 Secondary # UDACT Off Normal Code FF
171-172 Secondary # General Alarm Restore Code E1
173-174 Secondary # Zone/Point Alarm Restore Code 00
175-176 Secondary # General Supervisory Restore Code E2
177-178 Secondary # Zone/Point Supervisory Restore Code 00
179-180 Secondary # General Fault Restore Code E3
181-182 Secondary # AC Fault Restore Code E6
183-184 Secondary # Zone/Point Fault Restore Code 00
185-186 Secondary # Low Battery Fault Restore Code E8
187-188 Secondary # Telco Primary Line Fault Restore Code EA
189-190 Secondary # Telco Secondary Line Fault Restore Code EB
191-192 Secondary # NAC Fault Restore Code EC
193-194 Secondary # Comm.Trouble Primary Number Restore Code ED
195-196 Secondary # Comm. Trouble Secondary Number Restore Code EE
197-198 Secondary # 485 Comm. Trouble Restore Code EE
199-200 Secondary # System Off Normal Restore Code EF
201-202 Secondary # UDACT Off Normal Restore Code EF
203-204 Secondary # System 24 Hour Test 99
205-206 Secondary # System 24 Hour Test w/active event 91
207-208 Secondary # Manual Test 92
NOTE: Zero entries prevent the transmission of the report to the Central Station.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals