UDACT Instruction Manual — P/N 50050:M 12/18/2009 37
3+1, 4+1 Express and 4+1 Standard Formats Programming Instructions
3.5 3+1, 4+1 Express and 4+1 Standard Formats
3.5.1 Primary Number
If “0”, “2”, “4”, “6” or “8” are entered for address 16, the following data is automatically
programmed for the primary phone number event codes. Enter a “0” for the data setting to disable
the report. These formats do not support zone/point programming. For zone/point reporting, refer to
Contact ID.
Table 3.2 Event Codes, Primary Number
Address Description Setting
69 Primary # General Alarm Code 1
70 Primary # Zone/Point Alarm Code 0
71 Primary # General Supervisory Code 8
72 Primary # Zone/Point Supervisory Code 0
73 Primary # General Fault Code F
74 Primary # AC Fault Code F
75 Primary # Zone/Point Fault Code 0
76 Primary # Low Battery Fault Code F
77 Primary # Telco Primary Line Fault Code F
78 Primary # Telco Secondary Line Fault Code F
79 Primary # NAC Fault Code F
80 Primary # Comm. Trouble Primary # Code F
81 Primary # Comm. Trouble Secondary # Code F
82 Primary # 485 Comm. Trouble Code F
83 Primary # System Off Normal Code F
84 Primary # UDACT Off Normal Code F
85 Primary # General Alarm Restore Code E
86 Primary # Zone/Point Alarm Restore Code 0
87 Primary # General Supervisory Restore Code E
88 Primary # Zone/Point Supervisory Restore Code 0
89 Primary # General Fault Restore Code E
90 Primary # AC Fault Restore Code E
91 Primary # Zone/Point Fault Restore Code 0
92 Primary # Low Battery Fault Restore Code E
93 Primary # Telco Primary Line Fault Restore Code E
94 Primary # Telco Secondary Line Fault Restore Code E
95 Primary # NAC Fault Restore Code E
96 Primary # Comm.Trouble Primary Number Restore Code E
97 Primary # Comm. Trouble Secondary Number Restore Code E
98 Primary # 485 Comm. Trouble Restore Code E
99 Primary # System Off Normal Restore Code E
100 Primary # UDACT Off Normal Restore Code E
101 Primary # System 24 Hour Test 9
102 Primary # System 24 Hour Test w/active event F
103 Primary # Manual Test 9
NOTE: Zero entries prevent the transmission of the report to the Central Station.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals