UDACT Instruction Manual — P/N 50050:M 12/18/2009 41
Ademco Contact ID Format Programming Instructions
3.7 Ademco Contact ID Format
3.7.1 Primary Number
If “E” is entered for address 16, the following data is automatically programmed for the primary phone
number event codes. Enter a “000” for the data setting to disable the report.
Table 3.6 Ademco Contact ID, Primary Number
Address Description
Setting
1
1 Zero entires prevent the transmission of the report to the Central Station.
Group #
2
2 The Group # is automatically incremented for AM2020/AFP1010, NFS2-3030, NFS-
3030, NCA-2, and NCA applications.
Sensor #
69-71 Primary# General Alarm Code 110 00 000
3
3 Refer to Contact ID program locations 64 - 68.
72-74 Primary # Zone/Point Alarm Code
4
4 AFP-200 applications transmit by zone, not by point.
110
5
5 For control panels; System 500, System 5000, AFP-200, AFP-400, NFS2-640, NFS-
640, NFS-320, AFP1010, AM2020, NFS2-3030, NFS-3030, NCA-2, and NCA, the
factory default event code is 110 and reprogrammable. The AFP-400 and AFP-100are
unique in point reporting mode in that only the control module report codes are
programmable. The factory setting of report code 111 is fixed for addressable smoke
detectors and cannot be changed.
00 Note
6
6 The identification of the zone-device number is automatically transmitted by the UDACT
and is added to the main event code. See Table 5.3 for more information.
75-77 Primary # General Supervisory Code 200 00 000
3
78-80 Primary # Zone/Point Supervisory Code
4
200 00 Note
6
81-83 Primary # General Fault Code 300 00
84-86 Primary # AC Fault Code 301 00
87-89 Primary # Zone/Point Fault Code
4
380 00 Note
6
90-92 Primary # Low Battery Fault Code 302 00
93-95 Primary # Telco Primary Line Fault Code 351 00
96-98 Primary # Telco Secondary Line Fault Code 352 00
99-101 Primary # NAC Fault Code 321 00
102-104 Primary # Comm. Trouble Primary # Code 354 00
105-107 Primary # Comm. Trouble Secondary # Code 354 00
108-110 Primary # 485 Comm. Trouble Code 300 00
111-113 Primary # System Off Normal Code 308 00
114-116 Primary # UDACT Off Normal Code 350 00
117-119 Primary # System 24 Hour Test 602 00
120-122 Primary # System 24 Hour Test w/active event 608 00
123-125 Primary # Manual Test Message 601 00
126-128 Primary # General Security Code
7
7 The General Security Code applies to UL 864 9th Edition-listed Control Panels only.
130 00 000
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals