Function Code Table
MD380 User Manual
- 80 -
Chapter 5 Function Code Table
If FP-00 is set to a non-zero number, parameter protection is enabled. You must enter the
correct user password to enter the menu.
To cancel the password protection function, enter with password and set FP-00 to 0.
Group F and Group A are standard function parameters. Group U includes the monitoring
function parameters.
The symbols in the function code table are described as follows:
"
☆": The parameter can be modied when the AC drive is in either stop or running state.
"★
": The parameter cannot be modied when the AC drive is in the running state.
"●": The parameter is the actually measured value and cannot be modied.
"*": The parameter is factory parameter and can be set only by the manufacturer.
5.1 Standard Function Parameters
Function
Code
Parameter Name
Setting Range
Default Property
Group F0: Standard Function Parameters
F0-00 G/P type display
1: G type (constant torque load)
2: P type (variable torque load
e.g. fan and pump)
Model
dependent
●
F0-01 Motor 1 control mode
0: Sensorless ux vector control
(SFVC)
1: Closed-loop vector control
(CLVC)
2: Voltage/Frequency (V/F)
control
0 ★
F0-02 Command source selection
0: Operation panel control (LED off)
1: Terminal control (LED on)
2: Communication control (LED
blinking)
0 ☆
F0-03
Main frequency source X
selection
0: Digital setting (non-retentive at
power failure)
1: Digital setting (retentive at
power failure)
2: AI1
3: AI2
4: AI3
0 ★