NOTICE
Destruction of the drive converter
► If the error „ERROR GTR7 always ON“ occurs, the drive converter
must be disconnected from the mains supply within 5 minutes!
3.3.8 Power dissipation
Unit size 12 13 14
Power dissipation at nominal operating
1)
PD / W 155 185 250
Power dissipation at DC supply
1)
PD_dc / W 140 165 220
Table 21: Power dissipation
1)
Rated operation corresponds to UN=400 V; fSN; fout=50 Hz (typically value)
38
UNIT DATA