EasyManuals Logo
Home>Lennox>Industrial Equipment>G21Q Series

Lennox G21Q Series Unit Information

Lennox G21Q Series
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
FIGURE 64
TRANSDUCER
(PART #78H5401)
Page 48
To Measure Flame Signal−GC1 Ignition Control:
WARNING
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
GC1 FLAME SIGNAL TEST
FIGURE 63
IGNITION
CONTROL
SENSE" TERMINAL
SENSOR
WIRE
D.C.
MICROAMP
METER
FLAME SENSOR
(+)(−)
1 − Place meter in series between ignition control and sen
sor wire. Connect positive (+) lead of meter to ignition
control sensor connection and negative (−) lead of the
meter to sensor wire. See figure 63.
2 − Set thermostat for a heating demand and check flame
signal with unit operating. For G21/GSR21 series with
the GC1 ignition control (A3), a reading of 3 to 5 micro
amps DC is typical. The control will operate between 1
and 5 microamps DC.
Flame signal may rise above 3 to 5 microamps for the first
few seconds after ignition and then level off.
To Measure Flame Signal−GC3/G891 Ignition Controls:
A transducer (Part
#78H5401 avail
able from Lennox
Repair Parts) is re
quired to measure
flame signal on
GC3 / G891
equipped units.Seefigure 64. The transducer con
verts microamps to volts on a 1:1 conversion. GC3
flame signal is 1.5−2.5 microamps, therefore a read
ing of 1.5−2.5 volts should be read on the meter. G891
flame signal is 1.2−2.2 microamps, therefore a read
ing of 1.2−2.2 volts should be read on the meter. The
transducer plugs into the meter. See figure 66 for
proper use of transducer.
1 − Set the volt meter to the DC voltage scale. Insert
transducer into the VDC and common inputs. Ob
serve correct polarities. Failure to do so results in neg
ative (−) values.
2 − Turn off supply voltage to control.
3 − Disconnect flame sensor lead from terminal of ignition
control.
4 − Connect (+) lead of transducer to ignition control sen
sor connection. See figure 65.
5 Connect () lead of the transducer to sensor wire. See
figure 65.
6 Turn supply voltage on and close thermostat con
tacts to cycle system.
7 − When unit lights read voltage on meter display. Re
member 1 DC volt = 1 DC microamp. For G21/GSR21
series with the GC3 ignition control (A3), a reading of
1.5−2.5 volts DC should occur. For G21/GSR21 series
with the G891 ignition control (A3), a reading of 1.2−2.2
volts DC should occur.
SENSOR
WIRE
FIGURE 65
IGNITION
CONTROL
SENSE" TERMINAL
DIGITAL
METER
FLAME SENSOR
GC3 FLAME SIGNAL TEST
(+)
(−)
TRANSDUCER
FIGURE 66
TRANSDUCER USAGE
1 − Set meter to DC voltage scale.
2 − Insert transducer into the VDC and
Common inputs. Observe polarities
3 − Connect (+) end of transducer lead to
GC3 sensor terminal.
4 − Connect (−) end to sensor wire.
TRANSDUCER
PART no. 78H5401
(+) TO GC3
SENSOR
TERMINAL
SET DIAL TO MEASURE
VDC
(+)
(−)
(−) TO
SENSOR WIRE
NOTE−MUST USE
DIGITAL METER
RED COLLAR
INDICATES
POSITIVE
LEAD

Table of Contents

Other manuals for Lennox G21Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G21Q Series and is the answer not in the manual?

Lennox G21Q Series Specifications

General IconGeneral
BrandLennox
ModelG21Q Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals