9 System bus "CAN on board"
9.1 General information
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.1.4 Activating the bus terminating resistor
The CAN bus has to be terminated at the first and last physical node each by a resistor (120 Ω) bet-
ween CAN low and CAN high:
[9-1] Terminations at the beginning and end of the CAN bus
9.1.5 Setting baud rate & node address
The baud rate is set via code C351.
Options: 20, 50, 125, 250, 500, 1000 kbps
Lenze setting: 500 kbps
The node address is set via code C350
.
Valid address range: 1 to 63
8400
BaseLine C
CH
CL
CG
120 R
CAN
120 R
LOW
GND
I/OShields
CH
CL
CG
X1
HIGH
X13
Note!
The addresses of the nodes must differ from each other.