Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05 83
5 Motor control (MCTRL)
5.4 V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.3.1 Adapting the V/f base frequency
The V/f base frequency (C015) determines the slope of the V/f characteristic and has considerable
influence on the current, torque, and power performance of the motor.
The setting in C015
applies to all permitted mains voltages.
Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode) do not
need to be considered when the V/f base frequency is set. They are automatically compensated
for by the internal mains voltage compensation of the device.
Depending on the setting in C015
, it may be required to adapt the reference speed (C011) to tra-
verse the entire speed range of the motor.
In standard applications, the V/f base frequency (C015
) is set to the value of the rated motor fre-
quency (C089
) as a typical value and corresponds to the data of the motor nameplate.
Reference voltage for the V/f base frequency is the rated motor voltage (C090
) according to mo-
tor nameplate.
Note!
87-Hz operation
4-pole asynchronous motors which are designed for a rated frequency of f = 50 Hz in star
connection can be operated in delta connection when being constantly excited up to f =
87 Hz.
•Advantages:
Higher speed-setting range
73% higher power output in case of standard motors
Motor current and motor power increase by the factor .
The field weakening range starts above 87 Hz.
Generally, this process can also be used with motors which have different numbers of
pole pairs. In case of 2-pole asynchronous motors, the mechanical limit speed must be
maintained.
3

Table of Contents

Other manuals for Lenze 8400 BaseLine C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 BaseLine C and is the answer not in the manual?

Lenze 8400 BaseLine C Specifications

General IconGeneral
BrandLenze
Model8400 BaseLine C
CategoryInverter
LanguageEnglish

Related product manuals