8 Diagnostics & error management
8.6 Maloperation of the drive
154
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.6 Maloperation of the drive
Maloperation Cause Remedy
Motor does not rota-
te
DC-bus voltage is too low
• Red LED is blinking every 1 s
Check mains voltage
Controller is inhibited
• Green LED is blinking
Deactivate controller inhibit
• Note: Controller inhibit can be set via se-
veral sources !
• C158
displays all active sources for cont-
roller inhibit.
Automatic start is inhibited LOW/HIGH edge at RFR
If required, correct auto-start option in C142
.
"Inhibit at power-on" auto-start option
DC-injection braking (DCB) is active Deactivate DC-injection braking
Mechanical motor brake is not released Release mechanical motor brake manually or
electrically
Quick stop (QSP) active Deactivate quick stop
• Note: Quick stop can be set via several
sources!
• C159
displays all active sources for quick
stop.
Setpoint = 0 Select setpoint
Setpoint = 0 with activated fixed setpoint Set fixed setpoint in C039/1...3
Trouble is active Clear fault
With C006
= 4 zwar "SLVC: Vector control"
has been set, but no motor parameter identi-
fication has been carried out.
Carry out automatic motor parameter identi-
fication with the C002/23
device command.
Automatic motor data identification
Assignment of several mutually exclusive
functions with a signal source in C701
Correct configuration in C701.
Motor rotates irregu-
larly
Motor cable is defective Check motor cable
Maximum motor current in motor or genera-
tor mode is set too low
Adjust settings to the application: C022
:
Imax in motor mode
C023
: Imax in generator mode
Motor is underexcited or overexcited Check parameterisation:
C006
: Motor control
C015
: VFC: V/f base frequency
C016
: VFC: Vmin boost
Rated motor data (stator resistance, speed,
current, frequency, voltage) and cos ϕ and/
or magnetising inductance is not adapted to
the motor data
Carry out automatic motor parameter identi-
fication with the C002/23
device command
- or -
Adjust motor parameters manually:
C084
: Motor stator resistance
C087
: Rated motor speed
C088
: Rated motor current
C089
: Rated motor frequency
C090
: Rated motor voltage
C091
: Motor cosine phi
C092
: Motor magnetising inductance
Motor windings are wired incorrectly Reverse from star connection to delta con-
nection