EasyManuals Logo

Lenze 8400 BaseLine C User Manual

Lenze 8400 BaseLine C
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #256 background imageLoading...
Page #256 background image
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05 256
10 Parameter reference
10.2 Parameter list | C00142
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00142
C00144
Parameter | Name:
C00142 | Auto-start option
Data type: UNSIGNED_8
Index: 24433
d
= 5F71
h
Starting performance of the controller after mains connection and reset of "Trouble" or "Fault".
"Inhibit at power-on" auto-start option
Setting range (min. hex value | max. hex value) Lenze setting
0x00 0xFF 0x01 (decimal: 1)
Value is bit-coded: ( =bit set)
Bit 0 Inhibit at mains ON
Bit 1 Inhibit at trouble
Bit 2 Inhibit at fault
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00144 | Switching frequency reduction (temp.)
Data type: UNSIGNED_8
Index: 24431
d
= 5F6F
h
Activation of the automatic switching frequency reduction at too high temperature
Selection list (Lenze setting printed in bold) Info
0 Off Automatic switching frequency reduction deactivated
1On Automatic switching frequency reduction activated
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1

Table of Contents

Other manuals for Lenze 8400 BaseLine C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 8400 BaseLine C and is the answer not in the manual?

Lenze 8400 BaseLine C Specifications

General IconGeneral
BrandLenze
Model8400 BaseLine C
CategoryInverter
LanguageEnglish

Related product manuals