Basic units in the power range of 15 ... 90 kW
Wiring of the t erminals “controller inhibit (CINH)” when operating two function modules
7
Extensions for automation
7.4
7.4.6
L
7.4-14
EDS82EV903-1.0-11/2002
7.4.6 Wiring of the terminals “controller inhibit (CINH)” when operating two
function modules
)
))
) Note!
l Both terminals X3/28 of the interface FIF I and FIF II are
evaluated internally via an AND-operation.
l The following illustrations show possible methods of wiring.
Considering the AND-operation of both terminals X3/28, wiring
can be adapted to your application.
FIF I
39
7
+20V
2820
X3
GND3 GND1
62 9
7
20 28
E1 E2
E3
E4
39
A1
59
E82ZAFS
(PT E82ZAFS100)
E82ZAFx
FIF II
+20V
+5V
X3
GND1
GND2
0.5...0.6 Nm
4.4...5.3 lb-in
X3
PES
PES
0
8200vec262
Fig. 7.4-7 Wiring of the controller inhibit with internal voltage supply
0
For function modules with terminals X3/7 and X3/39: Fix a wire jumper between
X3/7 and X3/39
PES HF shield termination through large-surface connection to PE
Wiring of the other terminals: ^
Mounting Instructions for the function modules
FIF I
39
7
+20V
2820
X3
GND2 GND1
62 9
7
20 28
E1 E2
+
–
E3
E4
39
A1
59
E82ZAFS
(PT E82ZAFS100)
E82ZAFx
FIF II
+20V
24 V ext.
(
+30 V +0 %, max. 120 mA)
+12V-0%...
…
+5V
X3
GND1
GND2
0.5...0.6 Nm
4.4...5.3 lb-in
X3
PES
PES
0
8200vec263
Fig. 7.4-8 Wiring of the controller inhibit with external voltage supply
0
For function modules with terminals X3/7 and X3/39: Fix a wire jumper between
X3/7 and X3/39
PES HF shield termination through large-surface connection to PE
Wiring of the other terminals: ^
Mounting Instructions for the function modules
Internal supply voltage
External supply voltage 30