Parameter setting with the XT EMZ9371BC keypad
Remote parameter setting for system bus participants
9
Parameter setting
9.4
9.4.7
L
9.4-9
EDS82EV903-1.0-11/2002
9.4.7 Remote parameter setting for system bus participants
If controllers are networked via system bus (CAN) it is possible to remotely
parameterise all other system bus participants from one central place of the
network.
For this purpose use the menu ”Remote para”: 41
Step Keys Action
1. Select menu 3 ”Remote para”
zyZY
Change to the menu ”Remote para” with the arrow
keys
2. Change to the code level
Z
Display o f code C0370 ”CANremot para”
3. Change to parameter level
V
Display of the current parameter value:
”0” = OFF
4. Set the node address of the system
bus participant you want to
parameterise
A)
z
Select node address
Display of ”Nodexx”
B)
TV
Confirm node address
5. Change to the code level
A)
V
Display of operation level
B)
V
Display o f C0370 ”CANremot para”
6. Set parameters All settings are directed to the selected syst em bus
participant
7. Parameterise remotely other system
bus participants, if necessary
Restart ”loop” at step 1.
Do not forget to s witch off the remote p arameter setting after having completed the setting s:
8. Select menu 3 ”Remote para”
zyZY
Change to the menu ”Remote para” with the arrow
keys
9. Change to the code level
Z
Display o f code C0370 ”CANremot para”
10. Change to parameter level
V
Display of the node address ”Nodexx” activated last
11. Switch off the remote parameter
setting
y
Set ”0” = OFF
The remote parameter setting is completed
9.4.8 Menu structure
For easy operation, the codes are clearly arranged in function-related menus:
Main menu Submenus Description
No. Dis play No. Display
1 USER menu Defined codes in C0517
2 Code list All available codes
2.1 ALL All available codes in ascending order (C0001 ... C7999)
2.2 Para set 1 Codes i n parameter set 1 (C0001 ... C1999)
2.3 Para set 2 Codes i n parameter set 2 (C2001 ... C3999)
2.4 Para set 3 Codes i n parameter set 3 (C4001 ... C5999)
2.5 Para set 4 Codes i n parameter set 4 (C6001 ... C7999)