Decentralised supply (several supply terminals)
Decentralised supply with single-phase or two-phase mains connection
12
Network of several drives
12.7
12.7.1
L
12.7-1
EDS82EV903-1.0-11/2002
12.7 Decentralised supply (several supply terminals)
The controller DC bus is supplied through +U
DC
,-U
DC
via several controllers
connected to the mains in parallel. A 400 V mains can use one additional
regenerative power supply unit.
12.7.1 Decentralised supply with single-phase or two-phase mains connection
A 1
U
V
W
- U G
+ U G
A 2
U
V
W
- U G
+ U G
F 1 F 1 * F 1 F 1 *
Z 1 Z 1 *
Z 1 Z 1 *
F 4 F 5
F 4 F 5
K 1 0
L 1
P E
N / L 2
K 1 0 *
P E
L 1 L 2 L 3
P E
L 1 L 2 L 3
Fig. 12.7-1 Network of 230 V controllers with decentralised supply with single or two-phase
mains connection
A1, A2 230 V controller of 8200 vector series
Z1, Z1* Mains filters/mains chokes (¶ 12.5-2)
F1, F1* Mains fuses (¶ 12.4-6)
F4, F5 DC fuses (¶ 12.4-6)
K10, K10* Mains contactor
F1*, K10*, Z1* Only when connected to 2AC PE 180 V - 0 % ... 264 V +0 % , 48 Hz
-0 % ... 62 Hz +0 %
(
((
( Stop!
The following conditions must be met to ensure trouble-free
operation:
l General measures (¶ 12.4-1)
l In-phase connection on the mains side!
l With two-phase supply
– Cable/overload protection via a second assigned mains fuse
F1*
– Ensure current and power symmetry by a second mains
choke or mains filter Z1*
Block diagram
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E82EV751K4C and is the answer not in the manual?

Lenze E82EV751K4C Specifications

General IconGeneral
BrandLenze
ModelE82EV751K4C
CategoryDC Drives
LanguageEnglish

Related product manuals