Conditions for a trouble-free network of several drives
Fuses and cable cross-sections for a network of several drives
12
Network of several drives
12.4
12.4.4
L
12.4-6
EDS82EV903-1.0-11/2002
12.4.4 Fuses and cable cross-sections for a network of several drives
The values in the table apply to operation of controllers connected to the DC-bus
network with P
DC
= 100%, i.e. max. rated controller power on the DC-bus level.
(¶ 12.5-4)
For operation with reduced power it is possible to select smaller fuses and cable
cross-sections.
Type Fuse F1, F2, F3 E.l.c.b. Cable cross-section
1)
VDE UL VDE mm
2
AWG
E82EV551K2B M6A 5A B6A 1 18
E82EV751K2B M6A 5A B6A 1.5 16
E82EV152K2B M 10A 10A B 10A 1.5 16
E82EV222K2B M 16A 15A B16 A 2.5 14
E82EV551K4B M6A 5A B6A 1 18
E82EV751K4B M6A 5A B6A 1 18
E82EV152K4B M 10A 10A B 10A 1.5 16
E82EV222K4B M 10A 10A B 10A 1.5 16
9341 M 16A 15A 2.5 14
9342 M 32A 30A j6 10
9343 M 63A 60A 25 4
9364 M 100A 100A 50 1
9365 M 200A 200A 95 3/0
9321, 8241 M6A 5A C6A 1 18
E82EV551K4B, E82EV751K4B M6A 5A B6A 1 18
9322, 8242, 8211 M6A 5A C6A 1 18
8212 M6A 5A B6A 1 18
9323, 8243 M 10A 10A B 10A 1.5 16
E82EV152K4B, E82EV222K4B M 10A 10A B 10A 1.5 16
8213, 8214 M 10A 10A B 10A 1.5 16
9324, 8244 M 10A 10A B 10A 1.5 16
E82EV302K4B M 16A 15A B16A 2.5 14
8215, E82EV402K4B M 16A 15A B16A 2.5 14
9325, 8245, 8216 M 20A 20A B 20A 4 12
E82EV552K4B M 20A 20A B 20A 4 12
E82EV752K4B M 25A 25A B25 A 4 10
9326, 8246, 8217, 8218,
E82EV113K4B
M 32A 30A B 32A j6 10
9327, 8221, E82EV153K4B M 63A 60A 25 4
9328, 8222, E82EV223K4B M 80A 70A 25 4
9329, 8223, E82EV303K4B M 80A 80A 25 3
9330, 8224, E82EV453K4B M 125A 125A 50 0
9331, 8225, E82EV553K4B M 160A 150A 70 0
9332, 9333, 8226, 8227,
E82EV753K4B, E82EV903K4B
M 200A 200A 95 3/0
1)
Observe national and regional regulations (e . g. VDE0113, EN 60204)!
Mains input L1, L2, L3
Operation with mains
filter/mains choke