Operation with rated power (normal operation)
Rated data for mains voltage 500 V
4
Technical data
4.3
4.3.3
L
4.3-14
EDS82EV903-1.0-11/2002
Operation without mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV551K4C 0.55 M6 A B6 A 1 5A 18
E82EV751K4C 0.75 M6 A B6 A 1 5A 18
E82EV152K4C 1.5 M10 A B10 A 1.5 10 A 16
E82EV222K4C 2.2 M10 A B10 A 1.5 10 A 16
3
0
0
m
A
2
)
E82EV302K4C 3.0 M16 A B16 A 2.5 15 A 14
300 m
A
2
)
3
0
m
A
3
)
E82EV402K4C 4.0 M16 A B16 A 2.5 15 A 14
3
0
m
A
3
)
E82EV552K4C 5.5
3
/
P
E
A
C
M25 A B25 A 4 20 A 12
E82EV752K4C 7.5
3/PE AC
3
2
0
5
5
0
V
M32 A B32 A 6
4)
25 A 10
E82EV113K4C 11
320 ... 550
V
;
4
5
6
5
H
z
Operation only with mains choke
E82EV153K4B 15
45 ... 65 Hz
M63 A - 25 63 A 4 300 mA
E82EV223K4B 22
E82EV303K4B 30
E82EV453K4B 45
O
p
e
r
a
t
i
o
n
o
n
l
y
w
i
t
h
m
a
i
n
s
c
h
o
k
e
E82EV553K4B 55
Operation only with mains cho
k
e
E82EV753K4B 75
E82EV903K4B 90
Operation with mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV551K4C 0.55 M6 A B6 A 1 5A 18
E82EV751K4C 0.75 M6 A B6 A 1 5A 18
E82EV152K4C 1.5 M10 A B10 A 1.5 10 A 16
E82EV222K4C 2.2 M10 A B10 A 1.5 10 A 16
3
0
0
m
A
2
)
E82EV302K4C 3.0 M10 A B10 A 1.5 10 A 16
300 m
A
2
)
3
0
m
A
3
)
E82EV402K4C 4.0 M16 A B16 A 2.5 15 A 14
3
0
m
A
3
)
E82EV552K4C 5.5
3
/
P
E
A
C
M20 A B20 A 4 20 A 12
E82EV752K4C 7.5
3/PE AC
3
2
0
5
5
0
V
M20 A B20 A 4 20 A 12
E82EV113K4C 11
320 ... 550
V
;
4
5
6
5
H
z
M32 A B32 A 6
4)
25 A 10
E82EV153K4B 15
45 ... 65 Hz
M35 A - 10 35 A 8
E82EV223K4B 22 M50 A - 16 50 A 6
E82EV303K4B 30 M80 A - 25 80 A 3
E82EV453K4B 45 M100 A - 50 100 A 1 300 mA
E82EV553K4B 55 M125 A - 50 125 A 0
3
0
0
m
A
E82EV753K4B 75 M160 A - 70 175 A 2/0
E82EV903K4B 90 M200 A - 95 200 A 3/0
Fuse
E.l.c.b.
1)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic ”H” or ”K5”
2)
All-current sensitive e.l.c.b. for use with E82EVxxxK4C0xx
3)
All-current sensitive e.l.c.b. for use with E82EVxxxK4C2xx
4)
Flexible cable can only be connected using pin end connectors.
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)
Fuses and cable cross-sections
(operation with rated power,
mains voltage 500 V)
Show/Hide Bookmarks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze E82EV751K4C and is the answer not in the manual?

Lenze E82EV751K4C Specifications

General IconGeneral
BrandLenze
ModelE82EV751K4C
CategoryDC Drives
LanguageEnglish

Related product manuals