Registers
Modbus RS485 Interface
Operating Guide
- 69 -
Registers
Current Output Configuration
Register
#
Access
Rule
Current
Output
Name Data
Format
Description of
Attribute
Semantics of Values
Current Output Configuration
9100 Get/Set Output A Channel INT
Assigned Input Channel 1159 = Disabled
9150 Output B 1160 = Channel 1
9200 Output C 1161 = Channel 2
9250 Output D 1162 = Channel 3
9300 Output E 1163 = Unit Alarm
9350 Output F 1164 = Calculation 1
1165 = Calculation 2
9101 Get/Set Output A Source INT Input Source 1166 = Sensor
9151 Output B 1167 = Temperature
9201 Output C 1168
=
Pressure
9251 Output D
9301 Output E
9351 Output F
9102 Get/Set Output A Output INT Output Mode 1134 = 4-20mA
9152 Output B 1135 = 0-20mA
9202 Output C
9252 Output D
9302 Output E
9352 Output F
9103 Get/Set Output A Range* INT Range
*(Only available when
the range of Assigned
Input Channel is set to
Auto)
Refer To Tables 2 and 3
and Sensor Configuration
Manuals
9153 Output B
9203 Output C
9253 Output D
9303 Output E
9353 Output F
9104 Get/Set Output A On Error Action INT On Error Action 1130 = No Action
9154 Output B 1131 = Drive To 0mA
9204 Output C 1132 = Drive To 22mA
9254 Output D 1133 = Hold Level
9304 Output E 1134 = Drive to 4mA
9354 Output F
9105 Get/Set Output A Output Zero FLOAT Zero Equivalent Value Value depends on input
channel assigned to
9155 Output B
9205 Output C
9255 Output D
9305 Output E
9355 Output F
9107 Get/Set Output A Output Span FLOAT Current Output Span
Equivalent Value
Value depends on input
channel assigned to
9157 Output B
9207 Output C
9257 Output D
9307 Output E
9357 Output F