33
Automatic switch to backup heat source operation
Back-upheatsourceoperation(*1)willautomaticallyrunwhentheoutdoorunitstopsabnormally.Toenablethefunction,switchDIPSW2-5toON.Duringtheback-
upoperation,anerrorcode(s)andthecontactnumberwillbedisplayedalternately.Externaloutput(OUT11)willbeavailable.
Toclearthefault(s),resetthepowerbreakersontheindoorandoutdoorunits.
<Applicable error codes (*2)>
E6 to E9, ED, P6, P8, U1 to U8, UD, UE, UF, UL, UP
(*1)Prolongedrunningoftheback-upoperationmayaffectthelifeoftheheatsource.
(*2)Forsafetyreasons,thisfunctionisnotavailableforcertainfaults.(Systemoperationmustbestoppedandonlypumpkeepsrunning.)
6-19. DIP switch functions
Locatedonthe FTC printed circuit boardare4setsofsmallwhiteswitches
knownasDIPswitches.The DIPswitchnumberis printed onthecircuitboard
nexttotherelevantswitches.ThewordONisprintedonthecircuitboardandon
theDIPswitchblockitself.Tomovetheswitchyouwillneedtouseapinorthe
corner of a thin metal ruler or similar.
DIPswitchsettingsarelistedbelowinthetablebelow.
OnlyanauthorisedinstallercanchangeDIPswitchsettingunderone'sownre-
sponsibilityaccordingtotheinstallationcondition.
Beforechanging any switchsettings,ensurepowersuppliesto indoor andout-
doorunitsareisolated/poweredoff.
SW1
SW3
SW4
SW2
SW5
DIP switch Function OFF ON
Default settings:
Indoor unit model
SW1
SW1-1 Boiler WITHOUT Boiler WITH Boiler OFF
SW1-2 Heatpumpmaximumoutletwatertemperature 55ºC 60ºC ON
*
1
SW1-3 DHW tank WITHOUT DHW tank WITH DHW tank ON
SW1-4 Immersion heater WITHOUT Immersion heater WITH Immersion heater
OFF:
E**T20*-*C
ON : EH*T20*-*HC*
SW1-5 Booster heater WITHOUT Booster heater WITH Booster heater
OFF:
E**T20*-M*C*
ON :
E**T20*-*M 2/6/9*C
SW1-6 Booster heater function Forheatingonly ForheatingandDHW
OFF:
E**T20*-M*C*
ON :
E**T20*-*M 2/6/9*C
SW1-7 Outdoor unit type Split type Packagedtype
OFF: E*ST20*-*M**C*
ON :
EHPT20X-*M**C*
SW1-8 Wireless remote controller WITHOUT Wireless remote controller WITH Wireless remote controller OFF
SW2
SW2-1 Roomthermostat1input(IN1)logicchange
Zone1 operation stop at thermostat short Zone1 operation stop at thermostat open
OFF
SW2-2 Flowswitch1input(IN2)logicchange Failure detection at short Failure detection at open OFF
SW2-3 Booster heater capacity restriction Inactive Active
OFF:Except
EH*T20*-VM2*C
ON : EH*T20*-VM2*C
SW2-4 Coolingmodefunction Inactive Active
OFF: EH*T20*-*M**C*
ON :
ERST20*-*M**C
SW2-5
Automaticswitchtobackupheatsourceoperation
(When outdoor unit stops by error)
Inactive Active
*
2
OFF
SW2-6 Mixingtank WITHOUTMixingtank WITHMixingtank OFF
SW2-7 2-zonetemperaturecontrol Inactive Active
*
6
OFF
SW2-8 Flowsensor WITHOUTFlowsensor WITHFlowsensor ON
SW3
SW3-1 Roomthermostat2input(IN6)logicchange
Zone2 operation stop at thermostat short Zone2 operation stop at thermostat open
OFF
SW3-2 Flowswitch2input(IN3)logicchange Failure detection at short Failure detection at open OFF
SW3-3 Flowswitch3input(IN7)logicchange Failure detection at short Failure detection at open OFF
SW3-4 Electricenergymeter WITHOUTElectricenergymeter WITHElectricenergymeter OFF
SW3-5 Heatingmodefunction
*
3
Inactive Active ON
SW3-6 2-zonevalveON/OFFcontrol Inactive Active OFF
SW3-7 HeatexchangerforDHW Coil in tank ExternalplateHEX ON
SW3-8 Heat meter WITHOUT Heat meter WITH Heat meter OFF
SW4
SW4-1 — — — OFF
SW4-2 — — — OFF
SW4-3 — — — OFF
SW4-4
Indoorunitonlyoperation(duringinstallationwork)
*
4
Inactive Active OFF
SW4-5 Emergencymode(Heateronlyoperation) Normal
Emergencymode(Heateronlyoperation)
OFF
*
5
SW4-6 Emergencymode(Boileroperation) Normal Emergencymode(Boileroperation) OFF
*
5
SW5
SW5-1 — — — OFF
SW5-2 Advanced auto adaptation
*
7
Inactive Active
OFF:
Other than R1/R2 mode
ls
ON: R1/R2 models
SW5-3
SW5-4
SW5-5
SW5-6
SW5-7
SW5-8 — — — OFF
Notes: *1. When the cylinder unit is connected with a PUMY-P/SUHZ-SW outdoor unit of which maximum outlet water temperature is 55ºC, DIP SW1-2 must be changed to OFF.
*2. External output (OUT11) will be available. For safety reasons, this function is not available for certain errors. (In that case, system operation must be stopped and
only the water circulation pump keeps running.)
*3. This switch functions only when the cylinder unit is connected with a PUHZ-FRP outdoor unit. When another type of outdoor unit is connected, the heating mode
function is active regardless of the fact that this switch is ON or OFF.
*4. Space heating and DHW can be operated only in indoor unit, like an electric boiler. (Refer to "Indoor unit only operation" in page 61. )
*5. If emergency mode is no longer required, return the switch to OFF position.
*6. Active only when SW3-6 is set to OFF.
*7. SW5-2, "Advanced auto adaptation" is available only for R1 and R2 models.
SW5-3 SW5-4 SW5-5 SW5-6 SW5-7
E*ST20C-*M*C* ON ON ON ON OFF
E*ST20D-*M*C* ON OFF OFF ON OFF
EHPT20X-*M*C* OFF OFF OFF OFF OFF
Capacity code