<Thermistor adjustment>
Thisfunctionallows adjustmentstobemadetothethermistor readings from
−10to10°Cin0.5°Cintervals.
THW1: Thermistor(Flowwatertemp.)
THW2: Thermistor(Returnwatertemp.)
THW5: Thermistor(DHWtankwatertemp.)
THW6: Thermistor(Zone1owtemp.)(Option)
THW7: Thermistor (Zone1 return temp.)(Option)
THW8: Thermistor(Zone2owtemp.)(Option)
THW9: Thermistor (Zone2 return temp.)(Option)
THWB1: Thermistor(Boilerowtemp.)(Option)
THWB2: Thermistor (Boiler return temp.)(Option)
Auxiliarysettingsmenuscreen
<Auxiliary settings>
Thisfunctionisusedtosettheparametersforanyauxiliarypartsusedinthesystem
Menu subtitle Function/ Description
Economysettingsfor
pump
Water pump stops automatically in certain period of time from
whenoperationisnished.
Delay Timebeforepumpswitchedoff*
1
Electric heater
(Heating)
To select “WITH booster heater (ON)” or “WITHOUT booster
heater(OFF)”inHeatingmode.
Delay The minimum time required for the booster heater to turn ON
fromafterHeatingmodehasstarted.
Electric heater (DHW) Toselect"WITH(ON)"or"WITHOUT(OFF)"boosterheateror
immersion heater individually in DHW mode.
Delay The minimum time required for the booster heater or immersion
heater to turn ON from after DHW mode has started. (This
settingisappliedforbothboosterandimmersionheater.)
Mixing
valve
control *
2
Running Periodfromvalvefullyopen(atahotwatermixingratioof100%)
tovalvefullyclosed(atacoldwatermixingratioof100%)
Interval Interval(min.)tocontroltheMixingvalve.
Flow
sensor *
3
Minimum TheminimumowratetobedetectedatFlowsensor.
Maximum ThemaximumowratetobedetectedatFlowsensor.
*
1
Decreasing"timebeforepumpswitchedoff"mayincreasethedurationofstand-byin
Heating/Coolingmode.
*
2
SettheRunningtimeaccordingtothespecicationsoftheactuatorofeachmixingvalve.
It is recommended to set the interval to 2 minutes that is a default value. With the interval
setlonger,itcouldtakelongertowarmuparoom.
*
3
DonotchangethesettingsinceitissetaccordingtothespecicationofFlowsensor
attached to the cylinder unit.
Economy settings for pump
1.FromtheAuxiliarysettingsmenuhighlightEconomySettingsforwatercirculationpump.
2. Press CONFIRM.
3.Theeconomysettingsforwatercirculationpumpscreenisdisplayed.
4.UsebuttonF1toswitchtheeconomysettingsON/OFF.
5.UsebuttonsF3andF4toadjustthetimethewatercirculationpumpwillrun.(3–60
minutes)
Electric heater (Heating)
1.FromtheAuxiliarysettingsmenuhighlightElectricheater(Heating).
2. Press CONFIRM.
3.TheElectricheater(Heating)screenisdisplayed.
4.PressF1buttontoswitchthefunctionON/OFF.
5.UseF3andF4buttonstoadjustthetimeperiodofheatpumponlyoperation
beforetheboosterheaterwillassistinspaceheating.(5–180minutes)
Electric heater (DHW)
1.FromtheAuxiliarysettingsmenuhighlightElectricheater(DHW).
2. Press CONFIRM.
3. The Electric heater (DHW) screen is displayed.
4.PressF1andF2buttonstoswitchthefunctionON/OFF.(F1:boosterheater,
F2: immersion heater)
5.UseF3andF4buttonstoadjustthetimeperiodofheatpumponlyoperation
beforetheboosterheaterandtheimmersionheater(ifpresent)willassistin
DHWheating.(15–30minutes)
Electricheater(Heating)screen