Note
Refer to outdoor unit service manual for request code 0 to 102, 106 to 149.
Request codes 103 to 105 indicate error histories of both indoor and outdoor units.
As only 4 digits can be displayed at one time the software version number is displayed in two halves.
Entercode190toseetherst4digitsandcode191toseethelast4digits.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
Request code 200 resets all Function Setting to the factory default settings.
<Table 9-4-1>
Request
code
Request content Range Unit
103 Error history 1 (latest) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) Code
104 Error history 2 (second to last) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.)
105 Error history 3 (third to last) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.)
154 Watercirculationpump1-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
156 Watercirculationpump2-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
157 Watercirculationpump3-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
158 Watercirculationpump4-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
162 Indoorunit-DIPSW1settinginformation Refer to detail contents described hereinafter.
163 Indoorunit-DIPSW2settinginformation Refer to detail contents described hereinafter.
164 Indoorunit-DIPSW3settinginformation Refer to detail contents described hereinafter.
165 Indoorunit-DIPSW4settinginformation Refer to detail contents described hereinafter.
166 Indoorunit-DIPSW5settinginformation Refer to detail contents described hereinafter.
175 Indoorunit-Outputsignalinformation Refer to detail contents described hereinafter.
176 Indoorunit-Inputsignalinformation Refer to detail contents described hereinafter.
177 Mixingvalveopeningstep 0–10 Step
190 Indoorunit-Softwareversion1st4digits RefertoNotebelow.
191 Indoorunit-Softwareversionlast4digits RefertoNotebelow.
200 InitialisationofFunctionSetting
340 Watercirculationpump1-Accumulatedoperatingtimereset
342 Watercirculationpump2-Accumulatedoperatingtimereset
343 Watercirculationpump3-Accumulatedoperatingtimereset
344 Watercirculationpump4-Accumulatedoperatingtimereset
504 Indoor unit - Zone1 room temp. (TH1A) −39–88 °C
505 Indoor unit - Ref. liquid temp. (TH2) −39–88 °C
506 Indoorunit-Returnwatertemp.(THW2) −39–88 °C
507 Indoor unit - Zone2 room temp. (TH1B) −39–88 °C
508 Indoorunit-DHWtankwatertemp.(THW5) −39–88 °C
509 Indoorunit-Zone1owwatertemp.(THW6) −39–88 °C
510 Indoor unit - Outside air temp. (TH7) −39–88 °C
511 Indoorunit-Flowwatertemp.(THW1) −39–88 °C
512 Indoorunit-Zone1returnwatertemp.(THW7) −39–88 °C
513 Indoorunit-Zone2flowwatertemp.(THW8) −39–88 °C
514 Indoorunit-Zone2returnwatertemp.(THW9) −39–88 °C
515 Indoorunit-Boilerflowwatertemp.(THWB1) −40–140 °C
516 Indoorunit-Boilerreturnwatertemp.(THWB2) −40–140 °C
540 Flowrateoftheprimarycircuit 0–100 L/min
550 Indoor unit - Error postponement history 1 (latest)
Displays postponement code.
("––"isdisplaysifnopostponementcodeispresent.)
551 Indoor unit - Operation control at time of error 0 Standard, 1 Heater, 2 Boiler
552
Indoor unit - Operation mode at time of error 0:OFF,1:DHW,2:Heating,3:Cooling, 4:Legionellapreven-
tion,5:Freezeprotection,6:Operationstop,7:Defrost
553 Indoorunit-Outputsignalinformationattimeoferror Refer to detail contents described hereinafter.
554 Indoorunit-Inputsignalinformationattimeoferror Refer to detail contents described hereinafter.
555 Indoor unit - Zone1 room temp. (TH1A) at time of error −39–88 °C
556 Indoor unit - Zone2 room temp. (TH1B) at time of error −39–88 °C
557 Indoor unit - Ref. liquid temp. (TH2) at time of error −39–88 °C
558 Indoorunit-Flowwatertemp.(THW1)attimeoferror −39–88 °C
559 Indoorunit-Returnwatertemp.(THW2)attimeoferror −39–88 °C
560 Indoorunit-DHWtankwatertemp.(THW5)attimeoferror −39–88 °C
561 Indoorunit-Zone1flowwatertemp.(THW6)attimeoferror −39–88 °C
562 Indoorunit-Zone1returnwatertemp.(THW7)attimeoferror −39–88 °C
563 Indoorunit-Zone2flowwatertemp.(THW8)attimeoferror −39–88 °C
564 Indoorunit-Zone2returnwatertemp.(THW9)attimeoferror −39–88 °C
565 Indoorunit-Boilerflowwatertemp.(THWB1)attimeoferror −40–140 °C
566 Indoorunit-Boilerreturnwatertemp.(THWB2)attimeoferror −40–140 °C
567
Indoor unit - Failure (P1/P2/L5/L8/Ld) thermistor 0: Failure thermistor is none, 1: TH1A, 2: TH2, 3: THW1, 4:
THW2, 5: THWB1, 6: THW5, 7: THWB2, 8: TH1B, A: THW6, B:
THW7, C: THW8, D: THW9
568 Mixingvalveopeningstepattimeoferror 0–10 Step
569
OperatedFlowswitchattimeoffailure(L9) 0:Nooperatedflowswitch,1:Flowswitch1,2:Flowswitch2,
3:Flowswitch3
571 Flowrateattimeoferror 0–100 L/min
OCH570C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi EHST20C-VM2C and is the answer not in the manual?

Mitsubishi EHST20C-VM2C Specifications

General IconGeneral
BrandMitsubishi
ModelEHST20C-VM2C
CategoryHeat Pump
LanguageEnglish

Related product manuals