Note
Refer to outdoor unit service manual for request code 0 to 102, 106 to 149.
Request codes 103 to 105 indicate error histories of both indoor and outdoor units.
As only 4 digits can be displayed at one time the software version number is displayed in two halves.
Entercode190toseetherst4digitsandcode191toseethelast4digits.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
Request code 200 resets all Function Setting to the factory default settings.
<Table 9-4-1>
Request
code
Request content Range Unit
103 Error history 1 (latest) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) Code
104 Error history 2 (second to last) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) —
105 Error history 3 (third to last) Displayserrorhistory.("––"isdisplaysifnohistoryispresent.) —
154 Watercirculationpump1-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
156 Watercirculationpump2-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
157 Watercirculationpump3-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
158 Watercirculationpump4-Accumulatedoperatingtime(afterreset) 0–9999 10 hours
162 Indoorunit-DIPSW1settinginformation Refer to detail contents described hereinafter. —
163 Indoorunit-DIPSW2settinginformation Refer to detail contents described hereinafter. —
164 Indoorunit-DIPSW3settinginformation Refer to detail contents described hereinafter. —
165 Indoorunit-DIPSW4settinginformation Refer to detail contents described hereinafter. —
166 Indoorunit-DIPSW5settinginformation Refer to detail contents described hereinafter. —
175 Indoorunit-Outputsignalinformation Refer to detail contents described hereinafter. —
176 Indoorunit-Inputsignalinformation Refer to detail contents described hereinafter. —
177 Mixingvalveopeningstep 0–10 Step
190 Indoorunit-Softwareversion1st4digits RefertoNotebelow. —
191 Indoorunit-Softwareversionlast4digits RefertoNotebelow. —
200 InitialisationofFunctionSetting — —
340 Watercirculationpump1-Accumulatedoperatingtimereset — —
342 Watercirculationpump2-Accumulatedoperatingtimereset — —
343 Watercirculationpump3-Accumulatedoperatingtimereset — —
344 Watercirculationpump4-Accumulatedoperatingtimereset — —
504 Indoor unit - Zone1 room temp. (TH1A) −39–88 °C
505 Indoor unit - Ref. liquid temp. (TH2) −39–88 °C
506 Indoorunit-Returnwatertemp.(THW2) −39–88 °C
507 Indoor unit - Zone2 room temp. (TH1B) −39–88 °C
508 Indoorunit-DHWtankwatertemp.(THW5) −39–88 °C
509 Indoorunit-Zone1owwatertemp.(THW6) −39–88 °C
510 Indoor unit - Outside air temp. (TH7) −39–88 °C
511 Indoorunit-Flowwatertemp.(THW1) −39–88 °C
512 Indoorunit-Zone1returnwatertemp.(THW7) −39–88 °C
513 Indoorunit-Zone2flowwatertemp.(THW8) −39–88 °C
514 Indoorunit-Zone2returnwatertemp.(THW9) −39–88 °C
515 Indoorunit-Boilerflowwatertemp.(THWB1) −40–140 °C
516 Indoorunit-Boilerreturnwatertemp.(THWB2) −40–140 °C
540 Flowrateoftheprimarycircuit 0–100 L/min
550 Indoor unit - Error postponement history 1 (latest)
Displays postponement code.
("––"isdisplaysifnopostponementcodeispresent.)
—
551 Indoor unit - Operation control at time of error 0 Standard, 1 Heater, 2 Boiler —
552
Indoor unit - Operation mode at time of error 0:OFF,1:DHW,2:Heating,3:Cooling, 4:Legionellapreven-
tion,5:Freezeprotection,6:Operationstop,7:Defrost
—
553 Indoorunit-Outputsignalinformationattimeoferror Refer to detail contents described hereinafter. —
554 Indoorunit-Inputsignalinformationattimeoferror Refer to detail contents described hereinafter. —
555 Indoor unit - Zone1 room temp. (TH1A) at time of error −39–88 °C
556 Indoor unit - Zone2 room temp. (TH1B) at time of error −39–88 °C
557 Indoor unit - Ref. liquid temp. (TH2) at time of error −39–88 °C
558 Indoorunit-Flowwatertemp.(THW1)attimeoferror −39–88 °C
559 Indoorunit-Returnwatertemp.(THW2)attimeoferror −39–88 °C
560 Indoorunit-DHWtankwatertemp.(THW5)attimeoferror −39–88 °C
561 Indoorunit-Zone1flowwatertemp.(THW6)attimeoferror −39–88 °C
562 Indoorunit-Zone1returnwatertemp.(THW7)attimeoferror −39–88 °C
563 Indoorunit-Zone2flowwatertemp.(THW8)attimeoferror −39–88 °C
564 Indoorunit-Zone2returnwatertemp.(THW9)attimeoferror −39–88 °C
565 Indoorunit-Boilerflowwatertemp.(THWB1)attimeoferror −40–140 °C
566 Indoorunit-Boilerreturnwatertemp.(THWB2)attimeoferror −40–140 °C
567
Indoor unit - Failure (P1/P2/L5/L8/Ld) thermistor 0: Failure thermistor is none, 1: TH1A, 2: TH2, 3: THW1, 4:
THW2, 5: THWB1, 6: THW5, 7: THWB2, 8: TH1B, A: THW6, B:
THW7, C: THW8, D: THW9
—
568 Mixingvalveopeningstepattimeoferror 0–10 Step
569
OperatedFlowswitchattimeoffailure(L9) 0:Nooperatedflowswitch,1:Flowswitch1,2:Flowswitch2,
3:Flowswitch3
—
571 Flowrateattimeoferror 0–100 L/min