72
No. Fault symptom Possible cause Explanation - Solution
14 In2-zonetempera-
ture control, only
Zone2 does not
reach the set tem-
perature.
1. WhenZone1andZone2arebothinheating
mode,thehot water temperatureinZone2
doesnotexceedthatinZone1.
1. Normal action no action necessary.
2. Faultywiringofmotorizedmixingvalve 2. Refertoinstallationmanual,"5.3Wiringfor2-zonetemperaturecontrol".
3. Faultyinstallationofmotorizedmixingvalve 3. Checkforcorrectinstallation.(Refertothemanualincludedwitheachmotor-
izedmixingvalve.)
4. IncorrectsettingofRunningtime 4. CheckforcorrectsettingofRunningtime.
5. Motorizedmixingvalvefailure 5. Inspectthemixingvalve.(Refertothemanualincludedwitheachmotorized
mixingvalve.)
15
When a PUHZ-FRP
outdoor unit is con-
nected, DHW or Heat-
ingoperationcannot
run.
The outdoor unit is set to have operation of the
indoor unit of air conditioner take precedence over
that of the cylinder unit, and in the main remote
controllersettings"Electricheater(Heating)"or
"Electricheater(DHW)"isturnedoff.
TurnONElectricheater(Heating)or Electric heater(DHW)usingthemainre-
mote controller.
16 When a PUHZ-FRP
outdoor unit is con-
nected and is in heat
recovery operation,
the set temperature
is not reached.
Whentheoutdoorunitissettohavecooling
operation of the indoor unit of air conditioner take
precedence over that of the cylinder unit, the out-
door unit controls the frequency of the compres-
soraccordingtotheloadofairconditioner.The
DHWandheatingrunaccordingtothatfrequency.
Normal operation no action necessary.
IfAir-to-Watersystemisgiven priority in operation, compHzcanberegulated
dependingontheloadofDHWorHeating.Formoredetails,refertothePUHZ-
FRP installation manual.
17 After DHW operation
room temperature
risesslightly.
AttheendoftheDHWmodeoperationthe3-way
valvedivertshotwaterawayfromtheDHWcircuit
intospaceheatingcircuit.
This is done to prevent the cylinder unit compo-
nentsfromoverheating.
Theamountof hot water directed into thespace
heatingcircuit variesaccordingtothetype ofthe
systemandofthepiperunbetweentheplateheat
exchangerandthecylinderunit.
Normal operation no action necessary.
18
The room tempera-
turerisesduringDHW
operation.
3-wayvalvefailure Checkthe3-wayvalve.
(i)Manuallyoverride3-wayvalveusingthemainremotecontroller.(Referto
<Manualoperation>in "9-4. Service menu".)Ifthe3-wayvalvedoesnot
function,goto(ii)below.
(ii)Replace3-wayvalvecoil.Ifthe3-wayvalvecoilisreplacedbutthe3-way
valvedoesnotfunctiongoto(iii)below.
(iii)Replace3-wayvalve.(Referto"11.DISASSEMBLYPROCEDURE".)
19 Waterdischarges
from pressure relief
valve.
(Primary circuit)
1. If continual – pressure relief valve could bite
foreignobjectsandthevalveseatmaybe
damaged.
1. Turnthehandleonthepressurereliefvalveseveralturns.Ifleakagepersists,
replacethepressurereliefvalvewithanewone.
2. Ifintermittent–expansionvesselchargemay
have reduced/bladder perished.
2. Checkpressureinexpansionvessel.
Rechargeto1barifnecessary.
Ifbladderperishedreplaceexpansionvesselwithanewone.
20 Waterdischarges
from pressure relief
valve.
(Sanitary circuit)
1. Ifcontinual–eldsuppliedpressurereducing
valvenotworking.
1.
Checkfunctionofpressurereducingvalveandreplaceifnecessary.
2. If continual – pressure relief valve could bite
foreignobjectsandthevalveseatmaybe
damaged.
2. Turnthehandleonthepressurereliefvalveseveralturns.Ifleakagepersists,
replacethepressurereliefvalvewithanewone.
3. Ifintermittent–expansionvesselchargemay
have reduced/bladder perished.
3. Checkgas-sidepressureinexpansionvessel.
Rechargetocorrectprechargepressureifnecessary.
Ifbladderperishedreplaceexpansionvesselwithanewonewithappropriate
pre-charge.
4. DHWtankmayhavesubjectedtobackow. 4. Check the pressure in DHW tank. If pressure in DHW tank is similar to that in
theincomingmains,coldwatersupplythatmergeswithincomingmainswa-
tersupplycouldowbacktoDHWtank.Investigatesourceofback-feedand
rectifyerrorinpipework/ttingconguration.Adjustpressureincoldsupply.
21 Waterdischarges
from temperature
and pressure relief
valve
(EH*T20*-MHCW only)
(Sanitary circuit)
1. Ifcontinual–eldsuppliedpressurereducing
valvenotworking.
1. Checkfunctionofpressurereducingvalveandreplaceifnecessary.
2. If continual – temperature and pressure relief
valvecouldbiteforeignobjectsandthevalve
seatmaybedamaged.
2. Turn the handle on the temperature and pressure relief valve several turns.
Ifleakagepersists, replace thetemperatureandpressurereliefvalvewitha
newone.
3. Ifintermittent–expansionvesselchargemay
have reduced/bladder perished.
3. Checkgas-sidepressureinexpansionvessel.
Rechargetocorrectprechargepressureifnecessary.
Ifbladderperishedreplaceexpansionvesselwithanewonewithappropriate
pre-charge.
4. DHWtankmayhavesubjectedtobackow. 4. Check pressure in DHW tank. If pressure in DHW tank is similar to that in the
incomingmains,coldwatersupplythatmerges with incoming mains water
supplycouldflowbacktoDHW tank. Investigate source of back-feed and
rectifyerrorinpipework/ttingconguration.Adjustpressureincoldsupply.
5. Unit has overheated – thermal controls have
failed.
5. Switchoffpowertotheheatpumpandimmersionheaters.
Leavewaterrunning.
Waituntildischargestops.Isolatewatersupplyandreplaceiffaulty.